TECHNICAL  DATA,  M1500A

TAC Forta M1500A

Forta M1500A series Non-Spring Return linear actuators are
designed to mount directly on to VB-72xx two way globe
valve with a AV-811 

linkage kit

 (ordered separately) or VB-

8xxx two and three way globe valves and 

VB-9313-0-5-xx

three way globe valves with a AV-812 valve linkage kit (ordered
separately).

Applications include chilled or hot water and steam.
Field selectable input signals include reverse and direct
acting, Floating or Proportional 0-10, 2-10 vdc or 4-20 ma with
500 Ohm resistor (supplied) plus proportional sequencing
input signal ranges.

FEATURES
- Floating configuration controlled by a SPDT floating

controllers

- Proportional configuration 0-10, 2-10 vdc or 4-20 ma with

the addition of a 500 ohm resistor included
Direct/Reverse action switch selectable

- 337lbf (1500N) linear force
- 24 Vac powered
- Die-cast housing with plenum rated plastic cover for NEMA

2 (IP54) applications

- Manual override to allow positioning of valve
- Electronic valve sequencing and Electronic flow curve

(equal percentage or Linear) selection.

- Torque overload protection throughout stroke
- Easy “One Touch” input signal/stroke calibration

Stroke

>3/8" to 2" (9-52mm)

Stroke Timing

Floating 60 or 300 sec selectable
Proportional  15 sec @1/2" stroke

Feedback AO

2-10 vdc

Power Supply Type

Half Wave

Motor Type

Brushless  DC

Enclosure

NEMA 2 (IP 54) with both conduit
connectors used. NEMA 1 IP40 with
one connector used.

Sound Power Level

max 32 dba

Ambient Temperature
Storage

-13 °F-+149 °F (-25

- +65 

°C

)  ambient

Operational

122 °F (50 °C) For Chilled water
applications
113 °F (45°C) ambient at 281 °F
(138°C) Fluid temperature
107 °F (42 °C

)

ambient at 300 °F

(149 °C) Fluid temperature
100 °F (38 °C) ambient at 340 °F
(171

°

C) Fluid temperature

90°F (32°C) ambient at 366 °F
(186 °C) Fluid temperature

Min.  Operating  Temp.

14 °F (-10 °C)

Ambient Humidity

15 to 95 % RH non condensing

Materials
  Housing

Die-Cast Aluminum

  Cover

UL94 plenum rated plastic

Weight

3.96 lb (1.8kg)

Dimensions

Figure 1

Agency  Listings

UL873, cULus, C-tick, CE

Globe Valve Actuator General instructions

Model

Power

Running VA

Transformer

Size VA

Floating

Control

Proportional Control

Feedback

Force lbf

2-SPDT Aux 

Switch

M1500A

No

M1500A-S2

24vac 4a res

* 4-20mA with 500 ohm resistor

Yes

0-10vdc, 2-10vdc or

4-20mA*

2-10vdc

337 (1500 N)

Model Chart

24vac ±10%

50-60Hz

24

50

APPLICABLE LITERATURE

-

Forta/VB-7xxx Selection Guide, F-27490

-

Forta/VB-8xxx, VB-9xxx Selection Guide, F-27491

-

AV-811 Linkage VB-7xxx, F

-27442

-

AV-812

Linkage VB-8xxx, 

VB-9xxx, F

-27443

-

AV-800 Series Linkage Adapters

for Competitors Valves,

  F-27470

Summary of Contents for Forta M1500A

Page 1: ...ibration Stroke 3 8 to 2 9 52mm Stroke Timing Floating 60 or 300 sec selectable Proportional 15 sec 1 2 stroke Feedback AO 2 10 vdc Power Supply Type Half Wave Motor Type Brushless DC Enclosure NEMA 2...

Page 2: ...ide lowered MAN For normal operating the handle must be raised AUTO Position feedback M1500A actuators are equipped with a 2 10 vdc position feedback FUNCTION DIMENSIONS The actuator may be mounted ho...

Page 3: ...ed with 3 conductors with very long lengths floating control where control signal reference is connected to G the motor current of the actuator will cause varying voltage loss in the cable and thus in...

Page 4: ...DIM121E 4 10 F 27507 1 WIRING EXAMPLES Figure 6...

Page 5: ...5 10 DIM121E F 27507 1 Figure 7...

Page 6: ...f SW5 is ON the 5 10 6 10v is selected Note switch 5 is only active if switch 2 is OFF and switch 3 is ON 6 If switch 2 is ON SW6 controls run time SW 6 OFF equals 60 sec ON equals 300 sec run time 7...

Page 7: ...x and 82xx or 92xx Two Way Globe Valve Forta Proportional Control Setup Reference VB 8303 and VB 9313 Three Way Globe Valve Proportional Control Setup Reference Valve Type Valve position at low signal...

Page 8: ...Auxiliary Switch Optional Setup Reference Switch 1 CLOSE OPEN Switch 2 CLOSE OPEN of Valve Travel 0 10 20 30 40 50 60 70 80 90 100 With the actuator powered and being controlled by the input signal th...

Page 9: ...tions that are listed below Table 5 VB 8303 3 way valves Diverting Mixing Forta M1500A Base Floating Configuration Program Switch Position Desired Valve Operations Table 6 Auxiliary Switches 2 SPDT Cl...

Page 10: ...ts for class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installations This equipment g...

Reviews: