SYX66x Commissioning Guide
V1.10.3 300117
Page 32 of 61
8.
Menu Pages and Methods to Access Them
This manual shows all the menus and the settings contained on each page. The information is the same no matter
the interface method used:
•
Basic Web Browser
•
Web Browser with /mo/ feature
•
Colour Touchscreen
•
Controller LCD Interface
The images show on the following pages are from the Basic Web Browser. The user interface can be used to
achieve the same results. A Computer is not required to set the controller up however it is easier this way. No
matter the option used, the information at Level 2 Access is the same.
The main application settings can be changed in Level 2 only.
8.1
Starting the Controller
The controller goes through an initialisation procedure as it starts up. The outputs are all switched off until the
controller is ready.
The controller detects the connected sensors when it is powered up for the first time and it remembers the
connected sensors so that it may report alarms and correctly control the plant connected.
If you decide to remove sensors or have made errors in the wiring then the sensor allocations will need to be reset.
Please see page 49 for the procedure.
8.2
Connecting with a laptop
The controller is shipped with the following IP Address: 192.168.1.99/Subnet Mask 255.255.255.0/Gateway
192.168.1.1. Your laptop must be configured to be on the same IP address range. For more information on this task
please see a tutorial on this subject at http://www.syxthsense.com/video_resources.
8.3
Passcodes
Hold the ESC key for 5 Seconds to change user level, Press the wheel to select a number, Press Select button when
code complete to Enter it.
Level 0 = 0000, Level 1 = 1111, Level 2 = 0112, Level 3 = Reserved
8.4
Commissioning Mode (User Level 2)
The installer can put the controller into its commissioning mode when required. This allows the controller to by-
pass its energy saving features by switching the sensor readings to known values (Outside switched to 5’C and
Room switched to 18’C). The controller will observ
e all other functions. Times/Holidays/Extensions etc, the Heating
and HWS will operate as for a normal day using these values to calculate its set points.
8.5
Factory Defaults
Do not try to reset the controller. There is no factory default reset feature. Once parameters have been changed
they will be remembered by the controller even after power loss. The settings are documented in this manual and
they can be returned to default by setting them back to the values as shown on the following pages manually.
A controller that has been damaged or misapplied in any way will not be covered under warranty.