SYX66x Commissioning Guide
V1.10.3 300117
Page 13 of 61
4.2 Connection Diagram: Optimiser/Compensator Mode
•
One Space Sensor is required for the optimiser/compensator to function. The second is optional.
•
The HWS Control and its options are optional. IO-1RM is required if HWS output to be used.
•
The boilers serve the Heating and HWS Function (if linked)
•
Boiler Flow and Return Sensors are needed for boiler control
•
VT Flow Sensor required for Valve Compensation Control
•
Time Extend and Holiday features apply
•
0-10v Output option supported for the VT Valve, boiler demand or boiler set point control.
•
Heating is optimised on and optimised off as default. Optimum Off can be disabled meaning plant then turns off at
end of occupied period on Space High Temperature.
•
Observe KP10 sensor type polarity and GND connection see note Page 6
1 2
3 4
5 6
7 8
9 10
11 12
13 14 15 16 17 18
12vDC 0v
Space
1
Space
2
L
N
Boiler 1
Boiler 2
Pump
Open
Close
HWS
IO-
1RM
Outside
Temp
Heating
Return
Boiler
Flow
Optional
items
VT Flow
0-10v
Out
Day
Ext
Aux
Input
27 28 29 30 31 32 33 34 35 36
SYX66x
-ve
-ve