background image

6

installation manual 

Fig.5-11 

Fig.5-13  

Fig.5-12    

Body 

Panel foam2 

Ceiling 

Panel foam 

Air plate 

Panel 

Panel foam1 

Panel sealing foam 

Inlet air 

Outlet air 

Ceiling 

Leakage 

Dew 

Install  the  panel  on  the  main  body  with  bolt  (M5×16)  and  
washer.  

(Refer to Fig.5-11  ) 

Adjust  the  four  panel  hook  screws  to  keep  the  panel  
horizontal, and screw them up to the ceiling evenly.  

Regulate the panel in the direction of the arrow in  

Fig.5-11. 

slightly  to  fit  the  panel's  center  to  the  center  of  the  ceiling's  
opening. Guarantee that hooks of four corners are fixed well. 

Keep  fastening  the  screws  under  the  panel  hooks,  until  the  
thickness  of  the  sponge  between  the  body  and  the  panel's  
outlet  has  been  reduced  to  about  4~6mm.  The  edge  of  the  
panel should contact with the ceiling well. 

 (Refer to Fig.5-12) 

  

Malfunction  described  in  

Fig.5-13 

  can  be  caused  by  

inappropriate tightness the screw.  

If  the  gap  between  the  panel  and  ceiling  still  exists  after  
fastening the screws, the height of the indoor unit should  
be modified again.  

( Refer to Fig.5-14-left) 

You  can  modify  the  height  of  the  indoor  unit  through  the  
openings  on  the  panel's  four  cor ners,  if  the  lift  of  the  
indoor  unit  and  the  drainpipe  is  not  influenced  

(Refer  to  

Fig.5-14-right). 

Hang  the  air-in  grill  to  the  panel,  then  connect  the  lead  
terminator  of  the  swing  motor  and  that  of  the  control  box  
with corresponding terminators on the body respectively. 

Relocate the air-in grid in the procedure of reversed order,  
install the air-in grid. 

Cover 

Steel rope 

Swing motor installation cover 

Cover 

Steel rope 

Swing motor installation cover 

Swing motor side 

Drain side 

Bolt,  washer 

Fig.5-14 

Hexagon nut 

Ceiling 

Horizontal adjust ment 

Please operate according 
to the direction of the arrow, 
or it can not be disassembled 
when it is necessary. 

Connect the indoor unit at first, then the outdoor unit.

Bend the tubing in proper way. Don’t harm them.

Daub the surfaces of  the flare pipe and the joint nuts with 
refrigerant oil, and wrench it for 3~4rounds with hands before 
fasten the flare nuts. (Refer to 

Fig.6-1

 
Be sure to use two wrenches simultaneously when you connect 
or disconnect the pipes.

The stop valve of the outdoor unit should be closed absolutely 
(as original state). Every time you connect it, first loosen the nuts 
at the part of stop valve, then connect the flare pipe immediately 
(in 5 minutes). If  the nuts have been loosened for a long time, 
dusts and other impurities may enter the pipe system and may 
cause malfunction later. So  please expel the air out of the pipe 
with refrigerant before connection.

Expel  the air (refer to the “Expel The Air”) after connecting the 
refrigerant pipe with the indoor unit and the outdoor unit.Then 
fasten the nuts at the repair-points.

Notices For bendable pipe.

The bending angle should not exceed 90°C 

Bending position is preferably in the bendable pipe. The larger 
the better it is .

Do not bend the pipe more than three times.

Bend the connecting pipe of small wall thickness.

Cut out a desired concave at the bending part of the insulating 
pipe.

Then expose the pipe(cover it with tapes after bending).

To prevent collapsing of deforming, please bend the pipe at its 
biggest radius.

Use bender to get a small radius pipes.

Use the market brass pipe.
Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick).

● 

● 

● 

● 

● 

● 

● 

● 

● 

Ĺ

● 

ķ

ĸ

6.    INSTALL THE CONNECTING PIPE

Check  whether  the  height  drop  between the indoor unit and 
outdoor unit, the length of refrigerant pipe, and the number of the 
bends meet the following requirements:

The max height drop and The length of refrigerant pipe deponding 
on the ouotdoor unit.(If the height drop is more than 10m, you 
should put the outdoor unit over above the indoor unit.) 

The number bends fewer than 15

Do not let air, dust, or other impurities fall in the pipe system 
during the time of installation.

The connecting pipe should not be installed until the indoor and 
outdoor units have been fixed already.

Keep the connecting pipe dry, and do not let moisture in during 
installation.

The Procedure of Connecting Pipes
Measure the necessary length of the connecting pipe, and do the 
following:

● 

● 

● 

● 

● 

Summary of Contents for SYSVRF CASSETTE MINI

Page 1: ...SYSVRF CASSETTE MINI Cassette 600x600 VRF indoor unit INSTALLATION MANUAL GB...

Page 2: ...use injury The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The applia...

Page 3: ...liquid evaporating Other special conditions Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Improper installation work may result in the equipm...

Page 4: ...without further notices Cautions on remote controller installation Remote controller Remote controller holder Mounting screw B ST2 9x10 C H This manual Four way Cassette Four way Cassette compact INST...

Page 5: ...main body from the four sides or diagonal line direction the lever indicator also can check the lever from four sides of the main body Refer to Fig 5 6 Locate the air conditioner firmly by wrenching...

Page 6: ...i e h g n i l i e c H Horizontal indicator 45 5 3 Install The Panel Remove the air in grill Never put the panel face down on floor or against the wall or on uneven surfaces Never crash or strike it Sl...

Page 7: ...rant oil and wrench it for 3 4rounds with hands before fasten the flare nuts Refer to Fig 6 1 Be sure to use two wrenches simultaneously when you connect or disconnect the pipes The stop valve of the...

Page 8: ...or or soap water Cover the joint of the connecting pipe to the indoor unit with the sound proof insulating sheath fittings and bind it well with the tapes to prevent leakage Flaring Cut a pipe with a...

Page 9: ...76cmHg Loosen and remove the square cover of stop valves A and B to open stop valve A and B completely then fasten them Disassemble the charge hose from the repair mouth of stop valve A and fasten the...

Page 10: ...s should be incorporated in the fixed wiring according to the National wiring regulation Be sure to locate the power wiring and the signal wiring well to avoid cross disturbance and their contact with...

Page 11: ...ng Regulation Ground the air conditioner properly to obtain a good anti interference effect CAUTION Model W 1500 5600 15 15 3 2 0 Circuit breaker fuse A Indoor unit power wiring mm2 Indoor outdoor con...

Page 12: ...ation 1 means factory test mode 0 means add auto searching mode default setting 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fan static pressure is 0 reserved 01 means DC fan static p...

Page 13: ...f COOLING with the remotecontroller andcheckthefollowingpointsperthe Owner s Manual If there is any malfunction please resolve it as per chapter Troubles And Causes The indoor unit Whether the switch...

Page 14: ...SYSVRF CASSETTE MINI_IM EN April 2014 MDV11I 025EW...

Reviews: