English
Avoid contact with the coil surfaces and their sharp edges as they can be dangerous.
Caution
The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or
constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a
collapse with dangerous consequences for personnel and property. In such an event, the warranty
shall be null and void.
Caution
5
SysCoil Comfort
IMPORTANT
These datas are given for guidance only. They must be checked aat commissioning according to prevailing
standards. They depend on the installation and the cables used.
A main fuse must mandatorily be provided on the power supply.
²
Fuses not supplied
²
Cables not supplied
4.2.2. WITH ELECTRIC HEATING
Size
Electric heating capacity Fuse rating Gg
Fuse rating ASE / VDE Cable section mini
W
A
A
mm²
SCC10
500
4
10
3G1.5
SCC20
500
4
10
3G1.5
SCC30
500
4
10
3G1.5
1 000
4
10
3G1.5
SCC40
1 250
8
10
3G2.5
2 500
16
16
3G2.5
SCC50
1 250
8
10
3G2.5
2 500
16
16
3G2.5
SCC60
1 250
8
10
3G2.5
2 500
16
16
3G2.5
SCC70
1 250
8
10
3G2.5
2 500
16
16
3G2.5
SCC80
1 250
8
10
3G2.5
2 500
16
16
3G2.5
SEE APPENDIX
5. DIMENSIONS
6. HANDLING
6.1. NET WEIGHT
Always take great care when handling the unit.
Do not lift the unit by its condensate outlet, by the water
connectors and by the mounting lugs
.
Size
SCC10
SCC20
SCC30
SCC40
SCC50
SCC60
SCC70
SCC80
VC / HC
2 pipes kg
19
19
22
27
30
35
35
47
4 pipes kg
20
20
23
29
32
37
37
49
VN / HN
2 pipes kg
13
13
15
20
22
26
27
38
4 pipes kg
14
14
16
22
24
28
29
40
7. INSTALLATION
Important notes :
²
Inspect the fan coil unit nameplate sticked on the back of the unit chassis.
²
After installing the unit, please be sure that there is no more longitudinal and transversal
counterslopes avoiding condensate evacuation.
Summary of Contents for SysCoil Comfort SCC10
Page 2: ......
Page 23: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Page 41: ......