To perform electrical wiring of the unit, please refer to the wiring diagram pasted on the unit
casing.
Caution
12 SysCoil Comfort
SEE APPENDIX
All fan coil units are designed for operation under 230 volts, single phase, 50 or 60 cycles .
A voltage variation of ± 10 % with regard to nominal voltage 230 V is acceptable.
9. ELECTRICAL CONNECTIONS
WARNING
Before carrying out any work on the equipment,
make sure that the electrical power supply is
disconnected and that there is no possibility
of the unit being started inadvertently.
Non-compliance with the above instructions
can lead to injury or death by electrocution.
SE 4546
SysCoil Comfort AC motor terminal block
230V 50Hz/60Hz +/- 10%
SE 4548
SysCoil Comfort AC motor TBMV-4P/2PEH
230V 50Hz/60Hz +/- 10%
SE 4729
SysCoil Comfort AC motor SysLogic
230V 50Hz/60Hz +/- 10%
SE 4550
SysCoil Comfort EC motor terminal block
230V 50Hz/60Hz +/- 10%
SE 4552
SysCoil Comfort EC motor TBMV-4P/2PEH
230V 50Hz/60Hz +/- 10%
SE 4730
SysCoil Comfort EC motor SysLogic
230V 50Hz/60Hz +/- 10%
SE 4554
SysCoil Comfort EC motor terminal block without Ecospeed3
230V 50Hz/60Hz +/- 10%
SE 4555
SysCoil Comfort AC motor TBMV C/O
230V 50Hz/60Hz +/- 10%
SE 4556
SysCoil Comfort AC motor TBMV 2P/2P REV
230V 50Hz/60Hz +/- 10%
SE 4557
SysCoil Comfort EC motor TBMV 2P/2P REV
230V 50Hz/60Hz +/- 10%
9.1. WIRING DIAGRAM AND LEGEND
9.2. POWER SUPPLY
The electrical installation must be performed by a fully qualified electrician, and in accordance with local
electrical standards and the wiring diagram corresponding to the unit model.
Any modification performed without our prior authorisation may result in the unit’s warranty being declared
null and void.
The power supply cable section must be sufficient to provide the appropriate voltage to the unit’s power
supply terminals, both at start-up and under full load operating conditions.
The power supply cable shall be selected in accordance with the following criteria:
1.
Power supply cable length.
2.
Maximum unit starting current draw – the cables shall supply the appropriate voltage to the unit
terminals for starting.
3.
Power supply cables’ installation mode.
4.
Cables’ capacity to transport the total system current draw.
Short circuit protection shall be provided. This protection shall comprise fuses or circuit breakers with high
breaking capacity, mounted on the distribution board.
A device to disconnect all the power conductors with an approved minimum opening distance must be
included in the mains power supply according to best installation practices.