9
5.3 To install the product
For the installation on the wall measure the location and
size of the holes carefully:
• two wall openings for duct connections
• four drill holes (six holes for SNX 1000) at the ceiling for
unit installation (drill points marked in red).
Position of drill holes in the ceiling
Position of wall openings
First drill the holes into the wall for connection. After that,
drill the holes to the ceiling.
Caution
Dimension Bmin only corresponds to
installation where unit leans on the
back wall.
Note
M8 threaded rods with a distance of 500 mm is
availible as accessory.
D
A
L
1,min
R
1,min
H
1,min
D
L
2,min
R
2,min
B
min
E
E/2
E/2
F
Le
ft w
al
l
Righ
t w
al
l
Outer wall
SNX 700
SNX 1000
A
mm
1616
1800
B
min
mm
152
152
D
mm
315
315
E
mm
846
996
F
mm
2080
2350
H
1,min
mm
225
285
L
1,min
mm
732
775
R
1,min
mm
332
375
L
2,min
mm
475
475
R
2,min
mm
75
75
1. Unpack the product and place the product in the
correct installation position.
2. After the holes are drilled into the ceiling, install
threaded rods in length required for the specific room.
3. Gently lift the units from bellow. Use protective
clothing, so the unit’s surface does not get damaged.
4. Set the unit to required height with threaded rods
inside the brackets.
5. Install the washer and nut to bracket from bellow.
Note
Opening the unit before installation is not required.
Summary of Contents for Sense SNX
Page 1: ...Installation Operation and Maintenance instruction EN Sense...
Page 3: ...3...
Page 27: ...27...