SystemAir Sense SNX Installation,Operation And Maintenance Instruction Download Page 13

 

13

Fans

Both, supply and extract, fans have external rotor motors 
of EC type which are steplessly controlled individually by 

setting the control signal to a fixed value. Fans are set to 
preconfigurated 3 steps (minimum, medium, nominal) 

with boost setpoint. All 3 steps are possible to be 

reconfigured depending on the programming of the week 

schedule. The motor bearings are life time lubricated and 
maintenance free. It is possible to remove the fans for 
cleaning.

Filters

Due to geometry of the product and optimization of the 

internal airflow, the product consists of three filters. Out of 
those one is supply air panel filter with filter quality ePM1 

60% (F7). The other two are symmetrically positioned 

extract air bag filters with filter quality ePM10 60% (M5). 
The filters need to be replaced when polluted either 
with maximum pressure drop on supply filter or within 
one year, whichever happens first. The HMI display will 
show alarm when this happens. New sets of filters or 
higher quality filters can be acquired from your installer or 

wholesaler.

Heat exchanger

Units are equipped with a counter flow heat exchanger 

and a by-pass damper. The operation of the bypass 
damper is automatic and depends on the set temperature 
or if deicing is in operation. The heat exchanger is 
removable for cleaning and maintenance. 

Electrical heater (optional)

In air handling units with built in electrical preheater 
the heating rods are located between the supply air 

fan and heat exchanger in the airflow direction. In units 

with built in electrical reheater the heating rods are 
located between heat exchanger and supply air grille in 

the airflow direction. The material is stainless steel. The 

electrical heating battery has both automatic and manual 
overheating protection. The manual overheat protection 
is reset by pushing the red button on top of the electrical 
heater frame. The power demand of the electric heating 
coil is controlled by the main regulator, which controls 
the heat steplessly by a TTC triac control according to the 
selected control function that is set in the control panel.

Pressure sensors

Two pressure sensors are installed, each of the sensors 
has two functions. One function (A1) is to measure 
the differential pressure over the inlet cone of the fan 

impellers to maintain the airflow at constant level (CAV 

function as standard). The other function (A2) is to 
measure the dynamic differential pressure over the supply 

6. Commissioning

6.1 Description of internal components

air filter so that when the pressure drop reaches the set 

value, an alarm is triggered in the main regulator, which 

indicates that the filter needs to be replaced.

ODA

EHA

ETA

SUP

A2

B3

M3

B1

B2

B5

B4

M2

M1

A1

FS1

FS2+FS3

HE2

DB

HE1

B6+CO

CHE

Temperature sensors

Four temperature sensors (NTC 10K) are included in the 
unit from factory as standard. Additional two sensors 
come in case preheater is selected or CO

2

 sensor is added. 

The sensors are as follows:
•  (B1) Outdoor air temperature sensor
•  (B2) Supply air temperature sensor
•  (B3) Extract air temperature sensor
•  (B4) Exhaust air temperature sensor
•  (B5) Electrical preheater limiting sensor (options E01, 

E02, EE1, EE2)

•  (B6) Room temperature sensor (optional only with CO

2

 

sensor)

CO

2

 sensor (accessory)

CO

2

 sensors are used mainly for demand-controlled 

ventilation to prevent energy losses from over-ventilation 
while maintaining indoor air quality. Considering the 
installation of the product, positioning of the sensor will 

always be more than 2m above the floor.

Should the costumer want to instal wall sensor, they can 
connect it to controller inside electric cabinet on their 
own.

Free cooling

This function is used during the warm period to save 
energy by using cold outdoor air, e.g. during nighttime, to 
cool down the building and thereby reducing the need for 
cooling during the day time. 

Activation of the function occurs, when 
• 

Outside air (TOa) is sufficiently low compared to the 

apartment temperature (extract or room), 
•  and apartment temperature is above its actual 

se configurable hysteresis,

•  and outside temperature is above set minimum limit
• 

and free cooling is configured.

For deactivation a hysteresis of 2K (fix) is used. During 

activation, the operating mode is set to Comfort and 
kept there until one of the activation criteria is no longer 

fulfilled. In case of cascade control, the actual room 

temperature setpoint (depending on the operating 

Summary of Contents for Sense SNX

Page 1: ...Installation Operation and Maintenance instruction EN Sense...

Page 2: ...stall the product 9 5 4 To connect the product to the main power supply 10 5 5 To connect the ducts to the product 10 5 6 To connect the drainage onto the product 10 5 7 To connect the wall siphon to...

Page 3: ...3...

Page 4: ...cations where there is a risk of explosion The product is supplied with control system and constant air volume regulation CAV This document contains instructions for installation and commissioning of...

Page 5: ...00 700 m3 h 1000 1000 m3 h H Horizontal 000 No heaters E01 Preheater low power E02 Preheater high power 0E1 Reheater low power 0E2 Reheater high power EE1 Pre and reheater low power EE2 Pre and reheat...

Page 6: ...rvention The manufacturer reserves the right to modify these instructions without prior notice Caution It is recomended that installation and commissioning of the unit is done after all construction a...

Page 7: ...aged or wet during transportation A damaged or wet product can cause fire or electric shock Keep the product in a dry and clean location during storage Make sure that the ambient temperature during st...

Page 8: ...glands are tight against the cables to prevent leaks The unit should be stored and transported in such a way that it is protected against physical damage that can harm panels handles display etc It sh...

Page 9: ...ible as accessory D A L1 min R1 min H 1 min D L2 min R2 min B min E E 2 E 2 F Left wall Right wall Outer wall SNX 700 SNX 1000 A mm 1616 1800 Bmin mm 152 152 D mm 315 315 E mm 846 996 F mm 2080 2350 H...

Page 10: ...he ducts to the product 5 6 To connect the drainage onto the product The unit has a drip tray on the outer side on heat exchanger s extract air with drain pipe dimension of 18 mm Caution Should the in...

Page 11: ...drain pump to the product accessory Pump installation Open the accessory package containing drainage pump Loosen the screws of preinstalled kit securing the pump housing cover Remove the cap on the p...

Page 12: ...distance and lower supply air velocity turning blades into same direction to force supply air direction diagonally over room 2nd row of blades are horizontal and allow following turning blades slight...

Page 13: ...sure sensors Two pressure sensors are installed each of the sensors has two functions One function A1 is to measure the differential pressure over the inlet cone of the fan impellers to maintain the a...

Page 14: ...se damper reduce fan speed and increase preheating ERC maintain minimum exhaust temperature Maintain exhaust temperature and reduce fan speed Maintain exhaust temperature and increase preheating Maint...

Page 15: ...servise technician is needed for opening door 1 Remove all 3 screws on each door Use M6 imbus tool 2 On the back side near wall see the blocking element Warning Hold the door at all times before you...

Page 16: ...uired maintenance such as change of filters is carried out dust and grease may slowly build up inside the fans This will reduce the efficiency The fans The product has installed supply and extract air...

Page 17: ...ake care while inserting the left bag filter to slide it in next to control box 5 Close the door 6 In Alarm menu set Acknowledge alarm screen and press OK To change the filters To clean the heat excha...

Page 18: ...f all sensors fail Check connection of sensor and replace if needed 1014 B Extract air quality sensor fault System Run PmR or AQualR Particulate matters Air quality Stop control if all sensors fail Ch...

Page 19: ...l input Check if polarity is ok 2002 A Smoke detector Process Stop Smext BI Smoke extract mode Check connection of sensor and replace if needed 2004 A Fire alarm Process Stop Supply TSu or extract TEx...

Page 20: ...nd the commissioning report to Systemair The warranty is onlyapplicable for these conditions The product is correctly installed and operated The instructions in the data sheets are obeyed Maintenance...

Page 21: ...21 SNX 1000 all options have same geometry 2300 1800 250 250 996 2350 570 285 498 498 310 45 1 8 1200 45 510 390 1300 401 68 320 860 200 315 Outdoor air Supply air Extract air Exhaust air...

Page 22: ...ngth between room automation stations Max 30 m Number of devices in a line topology Max 20 Standard IT product at 100 MB BACnet on IP network Max length between two room automation stations 500 m Max...

Page 23: ...supply B Alarm indication voltage free contact C Contactor 11 2 To connect the HMI display 11 3 External connection Use 4 wire cable or UTP 5e cable for HMI connection Insert the other side of the cab...

Page 24: ...15 T12 T11 T16 T2 T18 T1 T5 KNX KNX Ref Ref Ref 24V 24V 5V X1 X2 X3 A1 A2 A3 A4 X8 B1 B2 B3 B4 Slave Master LAN Slave 1X3 C 1X3 1 2 1X3 C 24V DC 3 9 24V DC 6 0 24V DC 3 9 24V DC 6 0 24 1X3 24 SYSTEMAI...

Page 25: ...electromagnetic compatibility EMC 2014 30 EU EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 1 2019...

Page 26: ...ulations 2016 EN 62233 2008 Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure EN 61000 6 1 2019 Electromagnetic compatibility E...

Page 27: ...27...

Page 28: ...emair si Copyright Systemair d o o All rights reserved EOE Systemair d o o reserves the rights to alter their products without notice This also applies to products already ordered as long as it does n...

Reviews: