Instructions for unloading on the site as well as installation and connection |
27
The wiring diagrams are not unique for the order specific units, but it is standard wiring diagrams with data about all
configurations of the units. Hereby the wiring diagrams will inform about components that are not ordered and deliv-
ered. See the order confirmation and Annex 2 with exact information about the accessory components that are ordered
and delivered.
The wiring diagram includes:
• General description, Circuit diagrams, Cabinet layout, Terminal matrix and Cable plan.
• The wiring diagrams are on the DVD delivered with every unit.
I.3.2.1
Labels on or with the cabinet
• Label with data about the cabinet – including data about fuses – see chapter D.2.2
• Flowchart – see the example inchapter D.2.3 – unique flowchart for the order specific unit is shown in annex 2 with
the unique production number of the unit
• Label with an example of the terminal plan for external components is shown in chapter D.2.5 – the unique terminal
plan for external components for the order specific unit is shown in annex 2 with the unique production number of
the unit.
In chapter D.2.5 is for the Access control board shown a drawing of the control board with the terminals and this is just
an example, and not unique for the order specific unit.
I.3.3
Installation of mains power supply
An AC/DC residual current device must be installed in the power supply. The power supply for the units is 3*400 V + N
+ PE - 50 Hz. Protection of the units in accordance with the local statutory requirements for the additional protection of
systems with frequency converters and EC fans. The operator is responsible for the installation of the necessary protec-
tion equipment (supply disconnecting device is not delivered by Systemair.
I.3.3.1
Necessary mains power supply for units with cabinet/control system
Necessary mains power supply is printed on the unique machine card placed on the front of every unit (see example of
a machine card in chapter D.2.1).
I.3.3.2
Necessary overvoltage protection device, that leads lightning overvoltage to an
earth lead on a safe way.
The Installer and user must be aware of the fact that lightning strikes make a risk that requires installation of overvolt-
age protection devices to lead the lightning overvoltage to an earth lead in a safe way. Installer and user must take care
of this according to local statutory requirements.
I.3.4
Electrical connection of components and functions
External components and functions are delivered according to the order confirmation. Cable numbers appear from the
label inside or on the cabinet, and cable numbers appear from the wiring diagrams.
I.3.4.1
Video instruction — connection of the NaviPad control panel to the Access controller
Note:
Instructions about easy, quick and safe connection of the control panel to the controller in the cabinet
displayed in a 2–minutes video. The video is available on YouTube.
https://youtu.be/hmARvmUrbbU
The NaviPad control panel with touch screen is provided with 3 metres of cable for connection to the Access controller
inside the cabinet. Up to 100 m of cable between the Systemair NaviPad control panel and the Access controller is pos-
sible. Place the Systemair NaviPad control panel on the outer side of the unit or on a wall.
output |