23
15.
Possible alarms of additional electric heater
Before the start up, there will be an alarm because we do not have Terminal 3 and 4 from the electric
heater connected to the Terminals 29 and 30 in the electrical cabinet.
If we have connected the terminals then the reason is that maybe we forgot to configure to NC
contact in the menu:
If the alarm is active when the unit is running for some time, there will be an error electric heating is
overheated.
If the screen shows (picture bellow) the alarm ''Returned'', this means that the fault was removed
but the alarm was not confirmed. There was too hot in area of electric heater and automatic
thermostat disconnect power supply to contactor. Solution is that you need to increase airflow in
case if you have set point under minimum airflow:
To confirm an alarm press OK button and enter the password ''1111'' and ''Acknowledge''.
If the alarm is active and there is no ''Returned'' written then is probably still too hot in area of
electric heater. Wait 15min and if sign ''Returned'' appear then use solution from above.
If there is still alarm active after 15min then is probably triggered manual thermostat and its need to
be reset manually. If manual thermostat is OK and it’s still alarm then is something wrong with the
wire connection between terminal 29 and 30 from electric cabinet to terminal 3 and 4 to electric
heater.
DO NOT SET THE ALARM TO ''BLOCK'' STATUS
whit this we block alarm. When an error will appears
in system, it will not be displayed. This will possible damaged the system and the components or
there could be a fire outbreak!
Summary of Contents for FGT010
Page 1: ...Systemair FGT Control manual ...
Page 3: ...INSTRUCTIONS FOR CHANGING LANGUAGE CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 4: ...2 Contents 1 Search for change language menu 3 2 Changing language 4 ...
Page 10: ...4 Press OK button and you will be logged in as Admin ...
Page 13: ...7 3 Wiring diagram of ED TCV ...
Page 14: ...8 ...
Page 15: ...9 4 Wiring diagram of ED RU DFO ...
Page 16: ...10 ...
Page 18: ...INSTRUCTIONS FOR EXTERNAL SENSORS CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 28: ...11 Press OK button and you will be logged in as Admin ...
Page 34: ...INSTRUCTIONS FOR CHANGING AIRFLOW CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 35: ...2 Contents 1 Search for airflow set point menu 3 2 Airflow set point menu 4 ...
Page 50: ...12 And repeat process ...
Page 53: ...INSTRUCTION FOR CHANGING UNIT OPERATION TIME CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 60: ...INSTRUCTION FOR TURNING OFF THE UNIT CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 61: ...2 Contents 1 Search of running mode menu 3 2 Running mode menu 4 ...
Page 65: ...2 Contents 1 Search of changing temperature regulation menu 3 2 Temperature regulation menu 5 ...
Page 70: ...Contents 1 Search for temperature set point menu 3 2 Temperature set point menu 4 ...
Page 73: ...INSTRUCTIONS FOR WATER COOLER ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 87: ...INSTRUCTIONS FOR DX COOLING UNIT ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 90: ...4 Press OK button and you will be logged in as Admin ...
Page 95: ...9 5 Electric wiring diagram for DX cooler ...
Page 113: ...11 Press OK button 2x ...
Page 122: ...20 12 Electric wiring diagram of additional electric heater ...
Page 123: ...21 13 Electric wiring diagram of additional water heater ...
Page 126: ...INSTRUCTIONS FOR ELECTRIC HEATER ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 135: ...10 6 Electric wiring diagram ...
Page 136: ...11 7 2 phase electric heater diagram type MTXL ...
Page 137: ...12 8 3 phase electric heater diagram type MTXL ...
Page 140: ...INSTRUCTIONS FOR SMOKE DETECTOR CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...
Page 141: ...2 Contents 1 Basic information 3 2 Wiring 4 ...