30/49 |
FDS-3G…OF
Legend
F1
Screw ≥ 5,5 DIN7981 or suitable wall plug and screw size 6.
F5
Mineral wool segment (minimum 150 kg/m3).
F6
Layer of fire resistive coating (Promastop-CC/Promat) at least 2 mm thick for exposed surfaces.
F7
L-profile 60 × 40 × 3 mm, length W + 300 mm or WL + 300 mm
F8
Screw 3,9 × max. 13 DIN7504
1
Fire damper (actuator side)
2
Bendable hanger
3
Concrete/masonry/cellular concrete wall or ceiling
4
Flexible (plasterboard) wall
4a
2 layers of plasterboard fireproof plate type F, EN 520
4b
Vertical CW – profiles
4c
Horizontal CW – profiles
4d
Mineral wool; thickness/cubic density see picture.
5
Flexible (wood beam) wall
5a
Vertical spruce wooden beam ≥ 60 × 100 mm
5b
Horizontal spruce wooden beam ≥ 80 × 100 mm
6
Alternative thinner wall (classified in accordance with EN 13501-2:2007 + A1: 2009 for fire resistance required for
product application)
7
Area of 200 mm from opening around the damper must have the same composition and be created the same way as
Flexible (plasterboard) wall.
Notes:
ve
Vertical (wall)
ho
Horizontal (floor/ceiling)
1)
Smaller distances – resistivity maximum EI90 ( ve i<->o ) S
Summary of Contents for FDS-3G H0-OF Series
Page 1: ...FDS 3G OF Overflow Fire Damper FDS 3G ...
Page 14: ...14 49 FDS 3G OF Free area Dimensions Dimensions FDS 3G OF 200 x 200 up to 1200 x 800 ...
Page 15: ...15 49 FDS 3G OF Weights Overhangs ...
Page 18: ...18 49 FDS 3G OF Installation Methods ...
Page 21: ...21 49 FDS 3G OF ...
Page 25: ...25 49 FDS 3G OF ...
Page 29: ...29 49 FDS 3G OF ...
Page 32: ...32 49 FDS 3G OF ...
Page 34: ...34 49 FDS 3G OF ...
Page 49: ...Systemair DESIGN 2020 10 23 HandBook_FDS_3G_OF_en GB 8519DCD0 0720 11EB DCA1 21ABDD8D93BC ...