3/49 |
F-R60
Fire Damper F-R60
Description
Fire dampers represent passive fire protection and are designed to utilize compartmentalization to prevent the spread
of toxic gases, smoke and fire. The opening and closure of the damper blade can be activated remotely for actuator
versions. In case of fire when the air in the duct exceeds 72 °C or 74 °C, the thermal fuse melts in both actuator and
manual versions. The melting of the thermal fuse activates the closure of the damper blade automatically. The damper
blade is then mechanically locked in the closed position.
Highlights
• Short body
• Fire resistivity EI60S
• Interchangeable mechanism and actuator
• Manual mechanism with end position switches
• Casing leakage according to EN 1751, class C
• Blade leakage according to EN 1751, class 3
Fire Resistivity
F-R60 fire dampers are CE certified following the Construction Products Regulation according to EN 15650:2010.
Dampers are tested according to EN 1366-2:2015 and classified according to EN 13501-3 + A1:2009. The fire damper
together with its installation form an inseparable part of the fire resistivity rating. F-R60 fire dampers are designed for
the installations listed and described in their Handbook.
• Damper with standard supporting construction in accordance with EN 1366-2:2015:
EI60 (v
e
- h
o
i↔o)S
Accessory
Detailed information about accessories is available at design.systemair.com
• FCR: Flexible Duct Connection