Fin edges are sharp and can cause injury hazard. Avoid contact with them.
Caution
Avoid damaging the aluminium fins during cleaning. Never use pressurized water without a wide
diffuser. Concentrated and/or rotating water jets are strictly forbidden.
Caution
38 SYSAER R32
Clean the air exchanger using a special product for aluminium-copper coils and rinse with water. Do not use
hot water nor steam, as these may increase the refrigerating fluid's pressure.
18.3.1.4. AIR COOLED CONDENSER
Condenser coils are composed of copper tubes and aluminium fins. In case of leaks due to damage or
shock, the coils must be repaired by one of the authorized Support Centres. To guarantee the best possible
operation of the condenser bank, the condenser surface must be maintained as clean as possible, and it
must be void of foreign materials (leaves, wires, insects, slag, etc.). A dirty coil will see its absorbed electrical
power increase. In addition, condensation pressure could increase and trigger a high pressure alarm.
CAUTION
BEFORE CARRYING OUT ANY OPERATION ON THE EQUIPMENT, CHECK
THAT THE ELECTRICAL POWER SUPPLY IS SWITCHED OFF AND THAT IT
CANNOT BE SWITCHED ON INADVERTENTLY.
IT IS RECOMMENDED THAT THE DISCONNECT SWITCH BE PADLOCKED
Summary of Contents for AC-RSR105R32HEC