Installation instruction

EN

VAV duct pressure control kit

Summary of Contents for 145946

Page 1: ...Installation instruction EN VAV duct pressure control kit...

Page 2: ...ure sensors 3 4 3 3 To reset to factory settings 3 4 3 4 Status LED light 3 5 Technical data 4 5 1 Wiring diagrams 4 5 2 Topvex SR TR SC TC 4 5 3 Topvex FR FC SF 5 6 To configure the pressure transmit...

Page 3: ...ble 3 Tubes 4 Pressure measuring taps 2 Product liability Systemair is not liable for damages that the product causes in these conditions The product is incorrectly installed operated or maintained Th...

Page 4: ...e the installation of the product Examine the packaging for transportation damage and re move the packaging from the product carefully Examine the product and all components for damage 4 2 To install...

Page 5: ...4 ON 0 1000 2 OFF 3 ON 4 ON 0 1250 4 3 2 To zero point calibrate the pressure sensors 1 Disconnect the pressure ports before zero setting 2 Let the product warm up for 10 minutes before attempt ing t...

Page 6: ...act air PTS Pressure transmitter supply air T15 T16 Terminals in Topvex SR TR SC TC control unit G0 G 42 40 Terminals in Topvex FR FC SF control unit 5 2 Topvex SR TR SC TC WH YE BN YE BN GN GN WH WH...

Page 7: ...BN GB G G0 42 40 1 2 3 4 1 2 3 4 PTS PTE PTE PTS 6 To configure the pressure transmitter in the air handling unit controller 6 1 For SR TR SC TC FC FR 6 1 1 To log in 1 Open the log in window 2 Selec...

Page 8: ...ressure range in the pressure transmitter 1 Select Configuration from navigation icons 2 Select Configuration wizard 3 Select Set up pressure control 4 Set sensor range 5 Select In Outputs 6 Select Co...

Page 9: ...alog inputs use the navigation path Configuration I O allocation settings Analog inputs 10 Select Pressure extract air and repeat steps 7 and 8 6 1 5 To adjust the fan pressure set points Data setting...

Page 10: ...Auto Settings Configuration Access rights Sensor settings Control function Fan control Extra sequence Y4 Fan control Pressure control 6 2 3 To set the adjusted working range Set the adjusted working...

Page 11: ...tion Access rights Control temp Control pressure Alarm settings Alarm limits Alarm delays Restore alarm Control dev SAF 25 0 Pa Control dev EAF 25 0 Pa 6 2 6 To allocate in and outputs Menu level 1 Me...

Page 12: ...air AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair Sverige AB...