background image

Terminal Description

Table 1

BASES

Low Profile Base

Deep Base

Waterproof Base

INSTALLATION

Affix sounder Base
to a suitably flat
wall.
Terminate the
cable to the
appropriate
terminals.
Select the
appropriate Tone
and Volume
settings via the
DIP switch.
Locate the main assembly on to the base by rotating
until it locks into place.
The low profile base can be screwed to the deep base if
required using the two screws provided.

If the waterproof option
is required then the
wall gasket must be
fitted behind the deep
base, and the sealing o
ring fitted after
attaching the
low profile base.

CONTINUITY
SPRING

The sounder base incorporates a continuity spring
between terminals 2 and 3.  This allows the continuity of
the field wiring to be checked
without the need for the sounder to
be present.  Inserting the sounder
will disengage the spring.
Removing the sounder will close the
loop.   

ANTI TAMPER LOCK

The sounder base also includes a
tamper resistance feature that when
activated prevents removal of the unit without the use of
a tool.

To activate this feature, carefully,
using a pair of small pliers or
similar remove the tab section in
the wall of the sounder (as
shown). A sprung section of the
base will now snap into this
cavity upon installation of the
device. This prevents the device
being turned to enable its release. 
To remove the device once the
tamper resistance feature has
been activated,  place a small
bladed screwdriver into the small
hole on the side of the unit and
push the plastic lever into the
hole, away from the sounder. This
will allow the sounder to be rotated free of the plastic
arm. 
This feature is non-
reversible.

INSTALLATION INSTRUCTIONS FOR WMSOU WALL
MOUNTED LOOP POWERED ADDRESSABLE SOUNDERS.

MODELS

Non Isolation - 

WMSOU-RR-P01 

and 

WMSOU-WW-P01

With Isolation - 

WMSOU-RR-P02

and 

WMSOU-WW-P02

.

GENERAL

The WMSOU range of sounders is designed to be connected to
analogue addressable fire alarm systems. These sounders must
only be connected to control panels that use a compatible
proprietary analogue addressable communication protocol.
These devices receive their power from the loop, and can be
controlled via the communication protocol(s).  The sounders
have three volume levels and 32 tone sets.  Models WMSOU-
RR-P02 and WMSOU-WW-P02 include in built isolation
providing short circuit protection of the loop.

Up to 159 addresses are available. These are selected via the
two rotary selector switches. The 'tens' digits go from 0 to 150 (0
to F) and the 'units' from 0 to 9. See address settings on reverse.

Volume setting is selected by SW6 and SW7 of the 8 way DIP switch (see table 1). The appropriate tone set is
selected by SW1 to 5 of the 8 way DIP switch (see table 2).  The 2nd stage tone (related to the 1st stage tone) is
controlled by the fire panel via the protocol.

SPECIFICATIONS

Signalling Line Supply Voltage (non isolation) 15 to 32VDC (24VDC typical)
Signalling Line Supply Voltage (isolation) 15 to 28VDC (24VDC typical)

Max current consumption (High Volume Tone 24 @24V) <6.81mA
Max Output Power (High Volume Tone1 @24V) 100dB(A) +/- 3dB

Operating temperature range -25 to +70

o

C

Relative humidity up to 95% - non condensing

Terminal Connections (See table)
Terminal Size 2.5mm

2

- maximum

IP Rating
With Low profile base IP24
With Waterproof base IP65

SW6

SW7

Volume setting

OFF

OFF

HIGH

OFF

ON

MEDIUM

ON

OFF

LOW

ON

ON

LOW

Terminal

Function

T1

Negative

T2

Positive in

T3

Positive out

T4

N/C

T5

Shield

Gasket

O-Ring

D800 issue 8

Optional Earth Continuity Link

O-Ring

System Sensor Europe, Units 15-19 Trescott Road, Redditch, Worcestershire, England. B98 7AH.                                                                                        