SSM and SSV BELL Series

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Important

Please Read Carefully and Save

This  instruction  manual  contains  important  information 
about  the  installation  and  operation  of  bells.  Purchasers 
who install bells for use by others must leave this manual 
or a copy of it with the user.

System  Sensor  supplies  bells  for  nearly  all  sprinkler/fire 
alarm/burglar applications.

These instructions apply to all System Sensor bells in the 
series.  Read  all  instructions  carefully  before  beginning. 
Follow only those instructions that apply to the model you 
are installing.

Specifications

SSM Series:

Voltage:                                               Regulated 24 VDC
Operating Voltage Limit:                       16 - 33 VDC 
Maximum Current:                               DC - 31.1mA/FWR - 53.5mA
Operating Temperature:                        –31° to 150°F (–35° to +66°C)

SSV Series:

Voltage:                                               Regulated 120 VAC
Operating Voltage Limit:                       96 - 132 VAC
Maximum Current:                               53mA
Operating Temperature:                        –31° to 150°F (–35° to +66°C)

                                                                      

UL Reverberant Room

                                                          Sound Output per UL 464 (dBA)
24 VDC SSM

                                                                

SSM24-6           (6

, 24 VDC, P, S)                              82 

SSM24-8           (8

, 24 VDC, P, S)                              80 

SSM24-10          (10

, 24 VDC, P, S)                              81 

120 VAC SSV

                                                                

SSV120-6          (6

, 120 VAC)                                     85 

SSV120-8          (8

, 120 VAC)                                     82 

SSV120-10         (10

, 120 VAC)                                   82 

P = Polarized
S = Suppressed

NOTE: 

All SSM Series DC bells were only tested at the 

16–33 Volt-DC/FWR limits. All SSV Series AC bells were 
only tested at the 96–132 Volt AC limits. This does not 
include the 80% low-end or 110% high-end voltage limits.

General Description

The  National  Fire  Protection  Association  has  published 
codes,  standards,  and  recommended  practices  for  the 
installation  and  use  of  the  above  appliances.  It  is  recom-
mended  that  the  installer  be  familiar  with  these  require-
ments,  with  local  codes,  and  any  special  requirements  of 
the authority having jurisdiction.

These bells are intended to be connected to alarm indicat-
ing circuits of UL listed fire alarm control panels. The SSM 
series is polarized to enable supervision of the installation 
wiring.  The  SSM  bells  require  24  VDC  and  the  SSV  bells 
require 120 VAC.

CAUTION

Do not use in potentially explosive atmospheres.

Do not leave any unused wires exposed.