SpectrAlert Selectable Output
CH24MC Series Wall Chime/Strobes
for Fire Protective Signaling Systems

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: 

This  manual  shall  be  left  with  the  owner/user  of  this 

equipment.

General Description

The  SpectrAlert  CH24MC  series  strobe  can  be  installed  in  sys-
tems using 24-volt panels having DC or full-wave rectified (FWR) 
power supplies. The strobes can also be installed in applications 
requiring synchronization (MDL required) or applications that do 
not  require  synchronization  (no  module  required).  Please  note 
that the chime section is not synchronizable with the MDL.
The  SpectrAlert  CH24MC  series  chime/strobes  are  designed  to 
meet the requirements of most agencies governing these devices, 
including: NFPA, ADA, The National Fire Alarm Code, UL. Also, 
check  with  your  local  Authority  Having  Jurisdiction  for  other 
codes or standards that may apply.

NOTE:   The  SpectrAlert  CH24MC  Series  Chime/Strobe  must 

be  powered  from  a  non-coded  power  supply.  This 
appliance is not intended for use with a coded power 
supply.

Fire Alarm Considerations

Temporal and Non-Temporal Coded Signals:

The  American  National  Standards  Institute  and  the  National 
Fire Alarm Code require that all horns used for building evacu-
ation installed after July 1, 1996, must produce Temporal Coded 
Signals. Signals other than those used for evacuation purposes do 
not have to produce the Temporal Coded Signal. 

Power Supply Considerations For Strobes

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-wave 
rectified) voltage. The system design engineer must calculate the 
number of units used in a zone based on the  type of panel sup-

D900-38-00 

I56-2477-002R

For use with the following models: CH24MC and CH24MCW
U.S. Patent Nos. 5,931,569; 5.914,665; 5,850,178; 5,598,139; 6,049,446; 6,127,935; 6,133,843; 6,822,400; 6,856,241

Specifications: Chime

Mechanical

Input Terminals: 

12 to 18 AWG (3.31 to 0.82 mm

2

)

Overall Dimensions: 

6.9

 × 5.0

Electrical

Voltages: 

 Regulated 12 DC/FWR and  
Regulated 24 DC/FWR

Operating Voltage Limits: 

8–17.5 and 16–33

Maximum Operating Current
  At 12VDC: 

31 mA

  At 24VDC: 

61 mA

Operating Temperature: 

32°F to 120°F (0°C to 49°C)

Sound Output: 

Sound  output  levels  are  established 

at  Underwriters  Laboratories  in  their  reverberant  room.  Always 

use  the  sound  output  specified  as  UL  Reverberant  Room  when 
comparing products.
Listings: 

 UL  S4011  Private  Mode  (Chime/
Strobe), UL S5512 (Strobe)

Specifications: Strobe

Voltage: 

Regulated 24 DC/FWR

Operational Voltage Range:  16-33 Volts
Synchronous Applications
with MDL Module: 

17-33 Volts

Flash Rate: 

1 flash per second

Selectable Light Outputs: 

All  candelas  are  selectable  via  a 

manual slide switch. 15/75 is listed at 15 candela per UL 1971 but 
will provide 75 candela on axis (straight ahead). 15, 30, 75, or 110 
are rated for that candela.

ply. Be certain the sum of all the device currents does not exceed 
the  current  capability  of  the  panel.  Calculations  are  based  on 
using the device current found in Table 3 and must be the current 
specified for the type of panel power supply used. 

Wire Sizes

The designer must be sure that the last device on the circuit has 
sufficient  voltage  to  operate  the  device  within  its  rated  voltage. 
When  calculating  the  voltage  available  to  the  last  device,  it  is 
necessary to consider the voltage drop due to the resistance of the 
wire. The thicker the wire, the less the voltage drop. Generally, for 
purposes of determining the wire size necessary for the system, 
it is best to consider all of the devices as “lumped” on the end of 
the supply circuit (simulates “worst case”).
Typical wire size resistance:
18 AWG solid: 

Approximately 8 ohms/1,000 ft.

16 AWG solid: 

Approximately 5 ohms/1,000 ft. 

14 AWG solid: 

Approximately 3 ohms/1,000 ft.

12 AWG solid: 

Approximately 2 ohms/1,000 ft.

Example:  Assume  you  have  10  devices  on  a  zone  and  each 
requires  50  mA  average  and  2000  Ft.  of  14  AWG  wiring  (total 
length=ou return). The voltage at the end of the loop 
is 0.050 amps per device 

×

 10 devices 

×

 3 ohms/1,000 ft. 

×

 2000 

ft =3 volts drop.
The same number of devices using 12 AWG wire will produce only 
2 volts drop. The same devices using 18 AWG wire will produce 
8 volts drop. Consult your panel manufacturer’s specifications, as 
well as SpectrAlert’s operating voltage range to determine accept-
able voltage drop.
Note: If class “A” wiring is installed, the wire length may be up to 
4 times the single wire length in this calculation.

Note for Strobes: Do not exceed 1) 16-33 Voltage range limit, 2) Maximum number of 70 strobe lights when connecting the MDL Sync module with a maximum line imped-
ance of 4 Ohms per loop and 3) Maximum line impedance as required by the fire alarm control manufacturer.

Summary of Contents for SpectrAlert CH24MC Series

Page 1: ...s are established at Underwriters Laboratories in their reverberant room Always use the sound output specified as UL Reverberant Room when comparing products Listings UL S4011 Private Mode Chime Strobe UL S5512 Strobe Specifications Strobe Voltage Regulated 24 DC FWR Operational Voltage Range 16 33 Volts Synchronous Applications with MDL Module 17 33 Volts Flash Rate 1 flash per second Selectable ...

Page 2: ... limits Chime Selection Chimes are factory set for high volume 1 0K repeating 1 second chime Tones may be selected by making the appropriate settings on the DIP Switch located on the printed circuit board The set tings required for the available tone options are as follows Table 1 SpectrAlert Chime Switch Settings Switch 1 on 0 off 1 2 3 4 Hz Type 1 1 1 1 1 2k Repeating 1 Second Chime 1 0 1 1 1 0k...

Page 3: ...d plate is mounted vertically as shown B Mount the chime strobe using the 6 32 oval head screws The chime strobe shall be mounted on the left side of the mud ring The 6 32 screws shall be inserted into the holes on the mud ring that are opposite that of the strobes i e when the strobe is on the right screws into the left side of the mud ring and vice versa See Figure 1 To reverse the strobe module...

Page 4: ... power supply The chime will not work without power The chime gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the chime will not provide the desired audio or visual warning The chime may not be heard The loudness of the chime meets or exceeds current installation standards for private mode operation However the chime may not alert a sound ...