INSTALLATION AND MAINTENANCE INSTRUCTIONS

Selectable Output Strobes, Horns, and Horn/Strobes

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

D690-03-00 

I56-2769-003R

For use with the following models:  P2R, P2RH, P2RK, P2RHK, P2W, P2WH, P4R, P4RH, P4RK, P4RHK, P4W, P4WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH, 
PC2RK, PC2RHK, PC2W, PC2WH, PC4R, PC4RH, PC4RK, PC4RHK, PC4W, PC4WH, SCR, SCRH, SCRK, SCRHK, SCW, SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P, 
P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P, P4R-P, P4RH-P, P4W-P, P4WH-P, SR-SP, SRH-SP, P2R-SP, P2RH-SP, 
SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP

Specifications

General Specifications

Standard Operating Temperature: 

32°F to 120°F (0°C to 49°C)

K Series Operating Temperature: 

–40°F to 151°F (FM approved to –31°F); See note for Table 2.

Humidity Range: 

10 to 93% non-condensing (indoor products)

Strobe Flash Rate: 

1 flash per second

Nominal Voltage: 

Regulated 12DC/FWR or regulated 24DC/FWR

1

Operating Voltage Range: 

8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal)

Operating Voltage with MDL: 

9 to 17.5 V (12V nominal) or 17 to 33 V (24 V nominal)

1

P, S, PC,

 & SC produ

cts will operate at 12 V nominal only for 15 & 15/75 cd.

Mechanical Specifications

Input terminal wire gauge: 

12 to 18 AWG

Ceiling mount dimensions (including lens): 

6.8˝ diameter×2.5˝ high (173 mm diameter×64 mm high)

Wall mount dimensions (including lens): 

5.6˝L×4.7˝W×2.5˝D (142 mm L×119 mm W×64 mm D)

Horn dimensions: 

5.6˝L×4.7˝W×1.3˝D (142 mm L×119 mm W×33 mm D)

The products in this manual may be covered by one or more of the following patents: 
5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,522,261; 6,661,337; 6,822,400; 6,833,783; 6,856,241.

General Description

The  SpectrAlert  Advance  series  of  notification  appliances 
offers a comprehensive range of red and white wall, ceiling, 
and outdoor products including horns, strobes, and horn/
strobes. These products are electrically backward compat-
ible with the previous generation of notification appliances. 
While  there  are  products  specifically  designed  for  use  on 
the ceiling or the wall, the products are listed to be used 
in either application, i.e., wall products could be used on 
the  ceiling.  SpectrAlert  products  are  designed  to  be  used 
in either 12 or 24 volt DC or full wave rectified (FWR) sys-
tems. If required, the MDL module may be used in order to 
provide synchronization.

NOTICE:

 This manual shall be left with the owner/user of 

this equipment.

Fire Alarm System Considerations

The National Fire Alarm Code, NFPA 72, requires that all 
horns, used for building evacuation installed after July 1, 
1996, produce temporal coded signals. Signals other than 
those used for evacuation purposes do not have to produce 
the temporal coded signal.

Power Supply Considerations

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full 
wave rectified) voltage. The system design engineer must 
calculate the number of units used on a loop based on the 
type of panel supply. Be certain the sum of all the device 
currents does not exceed the current capability of the panel. 

Calculations are based on using the device current found 
in the subsequent charts and must be compatible with the 
current specified for the panel or power supply used.

Wire Sizes

The designer must be sure that the last device on the circuit 
has sufficient voltage to operate the device within its rated 
voltage. When calculating the voltage available to the last 
device, it is necessary to consider the voltage drop due to 
the resistance of the wire. The thicker the wire, the smaller 
the voltage drop. Generally, for purposes of determining the 
wire size necessary for the system, it is best to consider all 
of the devices as “lumped” on the end of the supply circuit 
to simulate worst case. For the most accurate voltage drop 
calculations use the System Sensor voltage drop calculator 
available on the web or CD-ROM.

Approximate wire resistance:

18 AWG solid:  8 ohms/1000 ft.
16 AWG solid:  5 ohms/1000 ft.
14 AWG solid:  3 ohms/1000 ft.
12 AWG solid:  2 ohms/1000 ft.

Note:

 If Class A wiring is installed, the wire length may be 

up to twice as long as on non-fault tolerant circuits.

Note:

 For 24 volt applications, the total number of strobes 

on a single NAC must not exceed 40, with a maximum loop 
resistance of 120 ohms. For 12 volt applications, the total 
number of strobes must not exceed 12, with a maximum 
loop resistance of 30 ohms.