D440-01-00
1
I56-0469-010
NOTICE:
This manual shall be left with the owner/user of
this equipment.
NOTE:
A test coil is required only for use with DH400/
DH500 models. For DH400 models order part # COIL400.
For DH500 models order part # COIL.
General Information
System Sensor’s RTS451 is an automatic fire detector acces-
sory designed to test a remotely located detector. Consult
detector installation instructions for additional information.
The National Fire Protection Association has published
codes, standards, and recommended practices for the in-
stallation and use of the above product. It is recommended
that the installer be familiar with these requirements, with
local codes, and any special requirements of the local au-
thority having jurisdiction.
RTS451 Contents
1 RTS451 remote test station
1 #4 screw for mounting bracket
1 screw pack (2 mounting screws)
1 M02-04 test magnet
Wiring of RTS451
Consult the appropriate detector installation instructions
for the applicable wiring diagram. The RTS451 mounts to
a single gang box (2
1
/
2
” minimum depth), or directly to the
wall or ceiling.
See
Figure 2
for wiring diagram of RTS451 with DH100ACDC
Duct Smoke Detector.
In Canadian applications, the RTS451 is intended to be lo-
cated in the same room as the smoke detector and within
60 feet of the unit.
Specifications
Dimensions:
4.6˝ H × 2.75˝ W × 1.5˝ D
Weight:
.11 lbs.
Power Requirements
Alarm LED:
2.8 – 32 VDC, 7.5 mA max.
Total Current:
105 mA max.
Test Switch:
10 VA @ 32 VDC
Reset Switch:
10 VA @ 32 VDC
Alarm Response Time:
40 sec. max.
Temperature:
–10°C to 60°C (14°F to 140°F)
Humidity:
95% RH Non-condensing
ALARM
RESET
M02-04
TEST MAGNET
LOCATIONS
Figure 1. RTS451 Remote Test Station:
RTS451 Remote Test Station
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Operation
Test Function
Place and hold the painted side of the magnet to the RTS451
on the right or left side of the LED as indicated in the dia-
gram above.
Alarm Indication
With the magnet in place some time will elapse (40 sec.
maximum) depending on the detector type, before the
alarm indicating LED will light.
Reset Function
Gently insert a
1
/
8
˝ maximum diameter tool into the hole un-
til it stops and LED turns off. The RTS451 is capable of reset-
ting only certain System Sensor models of detectors. Refer to
detector installation instructions for additional information.
H0196-00
I56-0469-0
10