NOTICE: 

This manual shall be left with the owner/user of 

this equipment.

NOTE:

  A  test  coil  is  required  only  for  use  with  DH400/

DH500 models. For DH400 models order part # COIL400.  
For DH500 models order part # COIL.

General Information

System Sensor’s RTS451 is an automatic fire detector acces-
sory  designed  to  test  a  remotely  located  detector.  Consult 
detector installation instructions for additional information.
The  National  Fire  Protection  Association  has  published 
codes,  standards,  and  recommended  practices  for  the  in-
stallation and use of the above product. It is recommended 
that the installer be familiar with these requirements, with 
local codes, and any special requirements of the local au-
thority having jurisdiction.

RTS451 Contents

1 RTS451 remote test station 
1 #4 screw for mounting bracket 
1 screw pack (2 mounting screws) 
1 M02-04 test magnet

Wiring of RTS451

Consult  the  appropriate  detector  installation  instructions 
for the applicable wiring diagram. The RTS451 mounts to 
a single gang box (2

1

/

2

” minimum depth), or directly to the 

wall or ceiling.
See 

Figure 2

 for wiring diagram of RTS451 with DH100ACDC 

Duct Smoke Detector.
In Canadian applications, the RTS451 is intended to be lo-
cated in the same room as the smoke detector and within 
60 feet of the unit.

Specifications

Dimensions: 

4.6˝ H × 2.75˝ W × 1.5˝ D

Weight: 

.11 lbs.

Power Requirements

 

Alarm LED: 

2.8 – 32 VDC, 7.5 mA max.

 

Total Current: 

105 mA max.

Test Switch: 

10 VA @ 32 VDC

Reset Switch: 

10 VA @ 32 VDC

Alarm Response Time: 

40 sec. max.

Temperature: 

–10°C to 60°C (14°F to 140°F)

Humidity: 

95% RH Non-condensing

ALARM

RESET

M02-04

TEST MAGNET

LOCATIONS

Figure 1. RTS451 Remote Test Station:

RTS451 Remote Test Station

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Operation

Test Function

Place and hold the painted side of the magnet to the RTS451 
on the right or left side of the LED as indicated in the dia-
gram above.

Alarm Indication

With  the  magnet  in  place  some  time  will  elapse  (40  sec. 
maximum)  depending  on  the  detector  type,  before  the 
alarm indicating LED will light.

Reset Function

Gently insert a 

1

/

8

˝ maximum diameter tool  into the hole un-

til it stops and LED turns off. The RTS451 is capable of reset-
ting only certain System Sensor models of detectors. Refer to 
detector installation instructions for additional information.

H0196-00

I56-0469-0