RA400Z and RA400ZA (Canadian) 
Remote Annunciator

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

General Information

The  National  Fire  Protection  Association  has  published 
codes,  standards,  and  recommended  practices  for  the 
installation  and  use  of  the  above  appliance.  It  is  recom-
mended  that  the  installer  be  familiar  with  these  require-
ments,  with  local  codes,  and  any  special  requirements  of 
the local authority having jurisdiction.

The  models  RA400Z  &  RA400ZA  remote  annunciators 
are polarized devices designed for both conventional and 
intelligent  applications.  They  have  been  designed  using 
an  active  current  regulator  so  that  the  maximum  current 
required from the system is 10mA when the input voltage 
is within the specified voltage range.

Installation

The  remote  annunciator  is  intended  to  be  mounted  to  a 
single  gang  electrical  outlet  box.  The  wiring  must  be  in 
compliance  with  all  codes.  The  device  must  be  operated 
within its published specifications.

Wire the remote annunciator according to the instructions 
supplied with the device being monitored. Polarity of the 
incoming  wires  must  be  observed  and  connected  to  the 
proper terminals “+” and “–”. (See Figure 1.) 

The  tab  on  the  back  of  the  RA400Z  and  RA400ZA  must 
be broken off for use with most System Sensor intelligent 
systems. (See Note 1 and Figure 4.) After tab is broken, the 
input voltage for the RA400Z and RA400ZA is limited to 18 
volts minimum.

H0355-00

Specifications

Voltage Range                               
        Conventional System:             3.1 to 32 VDC — Do not break tab.
        Intelligent System:                  18 to 32 VDC — Break tab.

NOTE 1

Maximum Alarm Current:               10 mA maximum.
Temperature Range:                        –10° to 60°C (14° to 140°F)

NOTE 1:

CAUTION

Do not break tab when using an RA400Z or RA400ZA with an intelligent 4-wire duct detector (such as the System Sensor 
model DH500ACDC or DH200RP).