System Sensor PIBVEXP Installation And Maintenance Instructions Download Page 1

D770-28-00 

I56-1430-002R

PIBVEXP Explosion Proof
Post Indicator and Butterfly Valve Switch

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Important

Please Read Carefully and Save

This  instruction  manual  contains  important  information 
on the installation and operation of supervisory switches.  
Purchasers who install supervisory switches for use by oth-
ers must leave this manual or a copy of it with the user. 
These instructions apply to System Sensor switches for post 
indicator  and  butterfly  type  valves.  Read  all  instructions 
carefully before beginning. Follow only those instructions 
that apply to the model being installed.

CAUTION

To prevent ignition of hazardous atmospheres, disconnect 
supply circuit before opening. Keep assembly tightly closed 
when in operation. Do NOT leave unused wires exposed.

All supervisory switch installations must comply with local 
codes and ordinances and the requirements of the author-
ity having jurisdiction. Additional information is available 
in National Fire Protection Association standards NFPA 13, 
13D, 13R, 71, and 72.

Specifications

Contact Ratings:               

One SPDT (Form C) Switch

 

 

 

 

15 A @ 125/250/480 VAC; 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC

 

 

 

 

1/2 A @ 125 VDC; 1/4 A @ 250 VDC

Dimensions:                    

3.75

L X 3.25

D X 4.5

H

Operating Temperature Range:    –40°F - 160°F (–40°C – 71°C)
Maximum Stem Extension:        2.1875

Shipping Weight:               

1-3/4 lb.                                                                                                                         

Enclosure Rating: 

 

UL Listed explosion proof switch enclosure for use in hazardous locations.

 

 

 

 

Class I, Groups C and D; Class II, Groups E. F and G

General  Information for Post Indicator Valves and 
Butterfly Valves

1.  Model  PIBVEXP  is  designed  for  installation  in  a 

1⁄2

  NPT 

tapped hole and located so that the actuating lever of the 
switch engages the target or flag of the valve . The switch 
actuating lever is spring loaded against the flag or target 
of the valve  and is released when the valve moves toward 
the closed position from the fully open position. 

2.  Model  PIBVEXP  is  equipped  with  a  removable 

1⁄2

  NPT 

pipe nipple which is locked in place with two set screws.

  A hex wrench is provided for this feature. These models also 

include  an  adjustable  length  actuating  lever  which  elimi-
nates any need for alteration of the length of the lever.