System Sensor P1R24110ADA Installation And Maintenance Instructions Manual Download Page 13

D900-02-00

1

I56-655-03

V4R24ADA Series Speaker/Strobes

for Fire Protective Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

General

The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the appliances described in these instructions. It
is recommended that the installer become familiar with
these standards and practices, local codes, and any special
requirements of the authority having jurisdiction.

The speakers can operate at any one of four input power
levels at either of two input voltages. The system voltage
and sound power levels are selected at the time of installa-
tion, but can be changed, if necessary.

Strobe

Specifications

Speaker

Frequency Range:

400 Hz to 4000Hz

Supervision:

Capacitive input for supervisory DC voltage

Mounting:

Standard 4" X 4" electrical box
Surface mount directly to box
Semiflush mount, using model MP-SF or MP-SFB

Model

Supply

Voltage

Range

Operating Current from

Regulated Supply

Operating Current from Full-Wave 

Rectified Unfiltered Supply

Average

Operating 

Current

Average

Operating 

Current

(mArms)

Peak

Current

(mA)

20Vrms/

30Vrms

Peak

Current

(mA)

20/30V

Inrush

Current

 (mA in
access

of Peak)

Inrush

Current

 (Amps in

excess

of Peak)

V4R24110ADA

V4R2475ADA

V4R2415ADA

V4R241575ADA

20-30V

210

470/500

0

245

400/500

0.08

20-30V

170

385/400

0

200

320/370

0.04

20-30V

 75

160/180

0

 90

275/290

0.02

20-30V

 93

210/220

0

120

275/290

1.0

NOTE:

 Inrush current duration is less than 20 microseconds (.00002 seconds).

Input

Voltage

(Vrms)

Power

Tap

(Watts)

Minimum Output (dBA)

UL

Reverberant

Anechoic

@ 10 ft.

25 or 70.7

1/4

75

78

25 or 70.7

1/2

78

81

25 or 70.7

1

81

84

25 or 70.7

2

84

87

The speaker is also equipped with a capacitive input to al-
low for DC supervision.

An attached 24 VDC strobe at 110, 75, 15, or 15/75 candela
(cd) is also included with the speaker. Although they are
assembled into a unit, the strobe and speaker are electri-
cally independent and require separate power sources.

Strobes can be powered by means of a full-wave rectified
unfiltered supply.

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for P1R24110ADA

Page 1: ...unfiltered supply Figure 1 Electrical connections Specifications Mechanical Input Terminals 12 to 18 AWG 3 31 to 0 82 mm2 Speaker Size 4 inches 101 mm Grille Size Round 7 3 8 187 mm Square 5 127 mm Electrical Voltage Input 25 volts or 70 7 volts nominal Frequency Range 400 4000 Hz Operating Temperature Range 32 to 120 F 0 to 49 C Installation All wiring must be installed in compliance with the Na ...

Page 2: ...ltage input power level combina tion being used NEVER connect the yellow jumper to the posts numbered 1 through 6 or the blue jumper to lettered posts A or B Mechanical Slotted head screws are included for attaching the speaker to the electrical junction box Insert the decorative filler plugs supplied into the remaining two holes in the grille Mounting See Figure 2 The speaker can be flush mounted...

Page 3: ...10 24M speaker w strobe speaker w strobe 24 24 25 mA 25 mA 45 mA rms 125 mA rms 1 5 cd 15 cd Strobe Light Ratings The signaling strobe is rated for 0 to 49 C and is not suit able for outdoor use See Figure 3 The light output of the SP10 24LO is 1 5 cd minimum when it is viewed from the front The light out put of the SP10 24M is 15 cd minimum when it is viewed from the front Under no circumstances ...

Page 4: ...s including this strobe are activated System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in materials and workmanship under normal use and service fo...

Page 5: ...ied unfiltered supply Installation For Strobe Replacement See NFPA 72 Chapter 6 All wiring must be installed in compliance with the Na tional Electrical Code and all applicable local codes as well as any special requirements of the authority having juris diction using the proper wire size This also includes all applicable NFPA Standards ANSI UL 1480 and NEC 760 Figure 1 Electrical connections Spec...

Page 6: ...ltage input power level combina tion being used NEVER connect the yellow jumper to the posts numbered 1 through 6 or the blue jumper to lettered posts A or B Mechanical Slotted head screws are included for attaching the speaker to the electrical junction box Insert the decorative filler plugs supplied into the remaining two holes in the grille Mounting See Figure 2 The speaker can be flush mounted...

Page 7: ...0 1 0 Note Inrush current lasts on the order of microseconds Table 3 SP100W24MC LO 1 5 cd UL 1638 Strobe M 15 cd UL 1638 Strobe 24 24 VDC Strobe SP100W Round Grille White Speaker SP101W Square Grille White Speaker SP101R Square Grille Red Speaker C Ceiling mount SP1R2415ADA 15 15 cd UL 1971 Strobe 1575 15 cd UL 1971 Strobe 75 75 cd UL 1971 Strobe 110 110 cd UL 1971 Strobe 24 24 VDC Strobe SP1R Squ...

Page 8: ...d System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in materials and workmanship under normal use and service for a period of three years from date ...

Page 9: ...0 Hz Supervision Capacitive input for supervisory DC voltage Grille Size 4 X 4 Cone Material Weather resistant Mounting Standard 4 X 4 electrical box Surface mount directly to box Semiflush mount using model MP SF or MP SFB red or beige Flush mount using Model MP F or MP FB Ceiling mount using flush mount kit MP F or MP FB Use Models SS24LOC and SS24MC Strobes optional for ceiling mounted installa...

Page 10: ...unting the speaker on the electrical box The other two holes will be used to attach the strobe and flush mount plate to the speaker c Position the strobe over the speaker and guide its two power lugs into the slots formed when the flash was removed in step 2 a Attach the strobe and flush mount plate to the speaker using 8 phillips head sheet metal screws through the pair of strobe mounting holes t...

Page 11: ...in the electrical box using two 8 32 X 2 3 4 screws 2 Speaker with Strobe Figure 7 a Use a small bladed screwdriver to remove the plastic flash from the two strobe blade slots on the speaker and flush mount plate b See Figure 3 Identify the two diagonally opposite speaker holes that will be needed for mounting the speaker on the electrical box The other two holes will be used to attach the strobe ...

Page 12: ...ng any of the methods described in this manual There fore follow the appropriate procedure to mount the speaker strobe on a ceiling 8 32x1 7 16 8 32x 1 7 16 8 S M 8 S M 6 32x5 8 6 32x5 8 8 NUTS V400 MP SF Plaster Ring Standard Backbox 8 32x5 8 A78 1799 02 Figure 8 Plaster Ring Mount 8 32x1 8 32x2 3 4 8 32x2 3 4 8 32x1 MP F V400 8 NUT 8 NUT BB D Signal Strobe Figure 7 Speaker Strobe Flush Mount A78...

Page 13: ...ing model MP SF or MP SFB Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 20 30V Inrush Current mA in access of Peak Inrush Current Amps in excess of Peak V4R24110ADA V4R2475ADA V4R2415ADA V4R241575ADA 20 30V 210 470...

Page 14: ...vice to the control panel must be broken at the device terminal con nection to ensure electrical supervision Figure 1 Vertical and horizontal light distribution Degrees of Rating 0 100 5 25 90 30 45 75 50 55 55 45 60 40 65 35 70 35 75 30 80 30 85 25 90 25 LIGHT 0 45 45 90 90 2 See Figure 2 The speaker is equipped with five posts and an associated plug with red and black wires The center post is CO...

Page 15: ...holes in the speaker strobe D Plaster Ring Mount See Figure 5 Follow the Semiflush Wall Mount proce dure except attach the semiflush plate to the electrical box using the two 6 32 X 5 8 screws 6 32x5 8 V400 8 32x1 7 16 8 Sht Mtl Signal Strobe 8 32x1 7 16 8 Sht Mtl 6 32x5 8 8 32x5 8 Figure 5 Plaster ring mount A78 1799 01 8 32x1 7 16 8 Sht Mtl 8 Sht Mtl 8 32x1 7 16 Signal Strobe V400 Figure 3 Surfa...

Page 16: ...robe must have an un interrupted source of DC power in order to operate correctly System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speakers and Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in ...

Reviews: