System Sensor M502MA Installation And Maintenance Instructions Download Page 1

  

I56-1051-002 

 

 7/1/2022

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to the con-
trol panel installation manual for detailed system information. If the modules will be 
installed in an existing operational system, inform the operator and local authority 
that the system will be temporarily out of service. Disconnect power to the control 
panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The M502MA Interface Module is intended for use in intelligent, two-wire systems, 
where the individual address of each module is selected using the built-in rotary 
switches. This module allows intelligent panels to interface and monitor two-wire 
conventional smoke detectors. It transmits the status (normal, open, or alarm) of one 
full zone of conventional detectors back to the control panel. All two-wire detectors 
being monitored must be ULC compatible with this module. The M502MA has a 
panel controlled LED indicator. M502MA is capable of handling more than one de-
tector in alarm condition.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
System Sensor system control panel only (list available from System Sensor). 

MOUNTING

The M502MA mounts directly to 4-inch square electrical boxes. (See Figure 2.) The 
box must have a minimum depth of 2.125 inches. Surface mounted electrical boxes 
(SMB500) are available from System Sensor.

FIGURE 1. CONTROLS AND INDICATORS

 

C1059-00

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and regula-
tions. This module is intended for power-limited wiring only.

1. 

 Install module wiring in accordance with the job drawings and appropriate wir-
ing diagrams.

2. 

Set the address on the module per job drawings.

3.   

Secure module to electrical box supplied by installer. (See Figure 2.) 

FIGURE 2. MODULE MOUNTING

ISOLATED 

QUADRANT

C1066-00

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 

 

M502MA Interface Module 

SPECIFICATIONS

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

5.1 mA (LED on)

Average Operating Current: 

270 µA (LED flashing)

EOL Resistance: 

3.9K Ohms

Maximum IDC Wiring Resistance:  25 Ohms
IDC Supply Voltage (between Terminals T10 and T11)
 

Regulated DC Voltage: 

24 VDC power limited

 

Ripple Voltage: 

0.1 Volts RMS maximum

 

Alarm Current: 

90 mA per module

 

Standby Current:  

13 mA Maximum @24 VDC

Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4.5˝ H × 4˝ W × 1.25˝ D (Mounts to a 4˝ square by 2.125˝ deep box.)

Accessories: 

SMB500 Electrical Box

I56-1

05

1-00

2