M500FP Firephone Control Module

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

Before Installing

This  information  is  included  as  a  quick  reference  installation 
guide. If the modules will be installed in an existing operational 
system, inform the operator and local authority that the system 
will be temporarily out of service. Disconnect power to the control 
panel before installing the modules.

NOTICE: 

This manual should be left with the owner/user of this 

equipment.

General Description

M500FP  Firephone  Control  Modules  are  intended  for  use  in  in-
telligent, two-wire systems, where the individual address of each 
module is selected using the built-in rotary switches. This module 
is used to connect a remote firefighter telephone to a centralized 
telephone console. A ringing sound is provided at each off-hook 
handset until it is connected to the console. Wiring to individual 
telephone  jacks  and  handsets  is  supervised,  and  status  is  re-
ported to the panel as NORMAL, TROUBLE, or TELEPHONE. The 
M500FP has two pairs of output termination points available for 
fault-tolerant wiring, and includes a panel-controlled LED indica-
tor.

Compatibility Requirements

To  ensure  proper  operation,  this  module  shall  be  connected  to 
Listed compatible system control panels only.

Mounting

This  module  mounts  directly  to  4

  square  electrical  boxes  (see 

Figure 2A). The box must have a minimum depth of 2

1

/

8

. Flush 

mounted electrical boxes (SMB500) are available.

Wiring

NOTE:

  All  wiring  must  conform  to  applicable  local  codes,  ordi-

nances  and  regulations.  When  using  control  modules  in 
nonpower limited applications, the CB500 Module Barrier 
must be used to meet UL requirements for the separation 
of  power-limited  and  nonpower-limited  terminals  and 
wiring. The barrier must be inserted into a 4

″ ×

 4

″ ×

 2

1

/

8

 

junction box, and the control module must be placed into 
the barrier and attached to the junction box (Figure 2A). 
The power-limited wiring must be placed into the isolated 
quadrant of the module barrier (Figure 2B).

Figure 1. Controls 
and Indicators

Figure 2A. Module mounting with barrier:

C0219-01

Figure 2B: 

C0217-01

C0218-01

Specifications

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

7.5mA (LED on).

Average Operating Current: 

2.4mA (LED flashing).

Handset Offhook Resistance: 

400 to 1,500 Ohms 

External Supply Voltage (between Terminals T3 and T4)
 

Regulated 24VDC

Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4

1

/

2

 H x 4

 W x 1

1

/

4

 D (Mounts to a 4

 square by 

2

1

/

8

 deep box.)

Accessories: 

SMB500 Electrical Box; CB500 Barrier

1.  Install module wiring in accordance with the job drawings and 

appropriate wiring diagrams (Figures 3-4).

2.  Set the address on the module per job drawings.
3.  Secure  module  to  electrical  box  (supplied  by  installer),  as 

shown in Figure 2A.

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

ISOLATED

QUADRANT

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

I56-1392-005

firealarmresources.com

Reviews: