M500DR Audio Control Module

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

Before Installing

This  information  is  included  as  a  quick  reference  installation 
guide. Refer to the control panel installation manual for detailed 
system information. If the modules will be installed in an existing 
operational system, inform the operator and local authority that 
the system will be temporarily out of service. Disconnect power to 
the control panel before installing the modules.

NOTICE: 

This manual should be left with the owner/user of this 

equipment.

General Description

M500DR  Audio  Control  Modules  are  intended  for  use  in  intel-
ligent,  two-wire  systems,  where  the  individual  address  of  each 
module is selected using the built-in rotary switches. This module 
is  used  to  select  either  one  of  two  separate  audio  signals,  then 
connect  it  to  a  speaker  circuit.  Wiring  to  the  speaker  circuit  is 
supervised,  and  status  is  reported  to  the  panel  as  NORMAL, 
OPEN, or SHORT CIRCUIT. The M500DR has two pairs of output 
termination  points  available  for  fault-tolerant  wiring,  and  does 
not  require  external  non-polarized  capacitors.  There  is  a  panel-
controlled LED indicator.

Compatibility Requirements

To  ensure  proper  operation,  this  module  shall  be  connected  to 
compatible system control panels only.

Mounting

This  module  mounts  directly  to  4

  square  electrical  boxes  (see 

Figure 2A). The box must have a minimum depth of 2

 

/

8

. Flush 

mounted electrical boxes (SMB500) are available.

Wiring

NOTE:

  All wiring must conform to applicable local codes, ordi-

nances and regulations. When using control modules in 
nonpower limited applications, the CB500 Module Bar-
rier must be used to meet UL requirements for the sepa-
ration of power-limited and nonpower-limited terminals 
and wiring. The barrier must be inserted into a 4

x4

x2

 

/

8

 junction box, and the control module must be placed 

into the barrier and attached to the junction box (Figure 
2A). The power-limited wiring must be placed into the 
isolated quadrant of the module barrier (Figure 2B).

Figure 1. Controls 
and Indicators

Figure 2A. Module mounting with barrier

C029-0

Figure 2B. Isolated Quadrant

C027-0

C028-0

Specifications

Normal Operating Voltage: 

5 to 32 VDC

Maximum Current Draw: 

6.5 mA (LED on)

Average Operating Current: 

390µA (LED flashing)

External Supply Voltage (between Terminals T2/T3 or T4/T5)
           Maximum: 

75 Volts RMS

Temperature Range: 

32˚F to 20˚F (0˚C to 49˚C)

Humidity: 

0% to 93% Noncondensing

Dimensions: 

4

/

2

 H x 4

 W x 

/

4

 D (Mounts to a 4

 square by 2

/

8

 deep box.)

Accessories: 

SMB500 Electrical Box; CB500 Barrier

.  Install module wiring in accordance with the job drawings and 

appropriate wiring diagrams (Figures 3-4).

2.  Set the address on the module per job drawings.
3.  Secure  module  to  electrical  box  (supplied  by  installer),  as 

shown in Figure 2A.

 3825 Ohio Avenue, St. Charles, Illinois 6074

-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

ISOLATED

QUADRANT

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

I56-1

390-00