background image

SS-300-022 

1 I56-3936-002R

d4240 duct Smoke detector

inSTaLLaTion and mainTenance inSTrucTionS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

TabLe of conTenTS 

Page

[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Exploded View of Duct Smoke Detector Components   . . . . . . . . . . . . . 2
[3] General Description   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Unit Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[10] Detector Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[11] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 6
[12] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Detector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[14] Sensor replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[15] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

 

before inSTaLLing

Read the System Sensor 

Guide for Proper Use of Smoke Detectors in Duct 

Applications

 (A05-1004), which provides information on detector spacing, 

placement, zoning, wiring, and special applications. This manual is available 
online at www.systemsensor.com. NFPA Standards 72 and 90A should also be 
referenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

I56-3936-00

2R

SPecificaTionS

Operating Temperature: 

D4240: –4° to 158° F (–20° to 70° C)

Storage Temperature: 

D4240: –22° to 158° F (–30° to 70° C)

Humidity: 

0% to 95% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

D4240 Footprint Dimensions: 

Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)

 

Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)

D4240 Weight: 

2.5 pounds; 1.14 kg

Electrical

Power supply voltage: 

20-29 VDC 

24 VAC 50-60-Hz 

240 VAC 50-60 Hz

Input capacitance: 

270 µF max. 

270 µF max. 

N/A

Reset Voltage: 

3.0 VDC min. 

2.0 VAC min. 

20 VAC min.

Reset Time (with RTS451/RTS151):  .03 to 0.3 sec. 

.03 to 0.3 sec. 

.03 to 0.3 sec.

Reset Time (by power down): 

0.6 sec. max. 

0.6 sec. max. 

0.6 sec. max.

Power Up Time: 

35 sec. max. 

35 sec. max. 

35 sec. max.

Alarm response time: 

15 sec. 

15 sec. 

15 sec.

Sensitivity Test: 

See detector label 

See detector label 

See detector label

Current Requirements (Using No Accessories)

Max. standby current 

21 mA @ 24 VDC 

65 mA RMS @ 24VAC 60Hz 

10 mA RMS @ 240 VAC 60 Hz

Max. alarm current 

65 mA @ 24 VDC 

135 mA RMS @ 24 VAC 60 Hz 

18 mA RMS @ 240 VAC 60 Hz

CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VDC (resistive)
Alarm auxiliary contatcs (DPDT) 10A @30 VDC (resistive) 

10A @250 VAC (resistive)

1

/

2

 HP @240 VAC

1

/

4

 HP @120 VAC

NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of 

control panels. Use the alarm initiation contact for this purpose.
Supervisory Contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE

STANDBY

TROUBLE

ALARM

APA151/APA451

12.5mA

n/a

30mA Max.

MHR/MHW

0mA

n/a

29mA Max.

RA400Z/RA100Z

0mA

n/a

12mA Max.

RTS451/RTS151

0mA

n/a

12mA Max.

RTS451KEY/RTS151KEY

12mA

n/a

12mA Max.

SSK451/RTS2-AOS

8mA Max.

16mA Max.

40mA Max.

NOTE: Any combination of accessories may be used such that the given 
accessory loads are: 110mA or less at the Aux output, and 50mA or less 
at the Alarm output.

IMPORTANT:

 This detector must be tested and maintained regularly following 

NFPA 72 requirements. The detector should be cleaned at least once a year.

[1] LimiTaTionS of ducT Smoke deTecTorS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The D4240 Air Duct Smoke Detectors 
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detector from activating 
when smoke is present in the air duct.

Summary of Contents for Inovair Flex D4240

Page 1: ...sing No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm i...

Page 2: ...city meter anemometer to check the air velocity in the duct 5 2 Determine Mounting location and Configuration On ducts wider than 18 inches it is recommended that the detector be mounted downstream of...

Page 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes Figure 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air cu...

Page 4: ...icate 2 sensors as shown in Figure 6 4 The D4S can only be used with new InnovairFlex models and is not com patible with previously sold detectors 9 Unit Configuration 9 unit configuration A three pos...

Page 5: ...contacts are not to be used for connection to the control panel See specifications for contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble conditio...

Page 6: ...igure 1 OR 1c Remote Test Accessory See list on page 1 The red alarm LED on the sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system contr...

Page 7: ...install the RTS451 RTS151 RTS451KEY RTS151KEY connect the device as shown in Figure 13 wire runs must be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel...

Page 8: ...minute tamper Delay if selected Off Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Term...

Reviews: