background image

SS-300-014 

1 I56-3050-004R

D2 Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Table of Contents 

Page

[1] Limitations of Duct Smoke Detectors  . . . . . . . . . . . . . . . . . . . . . . . . .1
[2] General Description   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[3] Contents of the Duct Smoke Detector Kit  . . . . . . . . . . . . . . . . . . . . . .1
[4] Exploded View of Duct Smoke Detector Components  . . . . . . . . . . . . .2
[5] Detector Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
[6] Sampling Tube Installation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
[7] Measurement Tests  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
[8] Field Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[9] Detector Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[10] Verification of Operator  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[11] Dectector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[12] Sensor Replacement  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
[13] Optional Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring Diagrams  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,6
Warranty 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

The D2 model is a photoelectric detector approved for an extended air speed 
range of 

100 to 4000 feet per minute

 (0.5 m/s to 20.3 m/s) and an operational 

temperature range of −4°F to 158°F (−20°C to 70°C).

BEfORE INSTALLINg

Read the System Sensor Guide for 

Proper Use of Smoke Detectors in Duct Appli-

cations

 (A05-1004), which provides detailed information on detector spacing, 

placement, zoning, wiring, and special applications. Copies of this manual 
are available online at www.systemsensor.com. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT:

 This detector must be tested and maintained regularly following 

NFPA 72 requirements. The detector should be cleaned at least once a year.

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The D2 Air Duct Smoke Detectors are 
listed per UL 268A.

This device will not operate without electrical power. Fire situations may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.

This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.

For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detector from activating 
when smoke is present in the air duct.

[2] gENERAL DESCRIPTION

Smoke introduced into the air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct. 

Model D2 Duct Smoke Detector utilizes photoelectric technology for the de-
tection of smoke. This detection method, when combined with an efficient 
housing design, samples air passing through the duct allowing detection of a 
developing hazardous condition. When sufficient smoke is sensed, an alarm 
signal is initiated and appropriate action can be taken to shut off fans, 
blowers, change over air handling systems, etc. These actions can facilitate 
the management of toxic smoke and fire gases throughout the areas served 
by the duct system.

[2.1] DETECTOR fEATURE SET

- Utilizes 2151 plug-in head

- Sampling tubes installed from front or rear

- Compatible with existing accessories

[3] CONTENTS Of ThE DUCT SMOkE DETECTOR kIT

1.  Sensor/power board assembly and covers
2.  Three #10 sheet metal screws for mounting
3.  Drilling template
4.  One sampling tube end cap
5.  One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must 
be the correct length for the width of the duct where it will be installed. See Ta-
ble 1 on page 3 to determine the inlet tube required for different duct widths. 

I56-3

05

0-004R

SPECIfICATIONS 

Operating Temperature: 

–4° to 158° F (–20° to 70° C)

Storage Temperature: 

–22° to 158° F (–30° to 70° C)

Humidity: 

0% to 93% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

Rectangular Footprint Dimensions: 

14.38 in L x 5 in W x 2.5 in D (37 cm L x 12.7 cm W x 6.36 cm D)

Square Footprint Dimensions: 

7.75 in L x 9 in W x 2.5 in D (19.7 cm L x 22.9 cm W x 6.35 cm D)

Weight: 

1.8 pounds; 0.82 kg

Electrical

Power supply voltage: 

8.5-35 VDC

Input capacitance: 

0.1 µF max.

Reset Voltage: 

2.5 VDC min.

Reset Time (with RTS451/RTS151): 

.03 to 0.3 sec.

Reset Time (by power down): 

0.3 sec. max.

Power Up Time: 

35 sec. max.

Alarm response time: 

15 sec.

Sensitivity Test: 

See detector label

Current Requirements (Using No Accessories)

Peak standby current 

120µA

Average standby current 

60µA

Max. alarm current 

130 mA

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

ALARM

RA400Z/RA100Z

0mA

12mA Max.

RTS451/RTS151

0mA

12mA Max.

RTS451KEY/RTS151KEY

0mA

12mA Max.

[1] LIMITATIONS Of DUCT SMOkE DETECTORS

Summary of Contents for Innovair flex D2

Page 1: ...n ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 General Description Smoke introduced into the air duct system will be distributed throughout the entire building Smoke detectors designed for use in air duct systems are used to sense the presence of smoke...

Page 2: ...EW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sa...

Page 3: ... open to ambient air measure and record the voltage drop across the 1000Ω resistor measurement 1 4 00 volts is typical Using flexible tubing and rubber stoppers connect the HIGH side of the transmitter to the sampling tube of the duct smoke detec 6 Sampling Tube Installation 6 1 Sampling Tube Selection The sampling tube must be purchased separately Order the correct length as specified in Table 1 ...

Page 4: ...e detector loop 8 1 Wiring Instructions The D2 detectors are designed for easy wiring The housing provides a ter minal strip with clamping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 6 below for system wiring 9 DETECTOR STATUS INDICATION Detector status is indicated by the LED s on the sensor Refer to tab...

Page 5: ...r With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray aerosol smoke into the duct through the 1 4 inch hole for five seconds Wait two minutes for the duct smoke detector to alarm If the duct smoke detector alarms air is flowing through the detector Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber ...

Page 6: ...___ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for brea...

Reviews: