background image

D200-101-01

4

I56-6574-000  

WIRING INSTALLATION

Power, Alarm and Control Connections

Figure 9: Inside the Detector

CHANNEL 2 FILTER

POWER AND 

ALARM 

CONNECTIONS

CHANNEL 1 FILTER

USB PORT

SENSOR      COVER

POSITION FOR 

TEST MAGNET

Exhaust Pipe

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1

7 18

5

6

EARTH BAR

MOUNT

EARTH BAR

MOUNT

F-LT-EB

EARTH BAR

(OPTIONAL)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

3

4

Note 1: All wiring should comply with local 

requirements and regulations. 
Note 2: Panel wiring must observe the 

recommendations of the panel manufacturer

PLACE 

WIRING 

LABEL 

HERE

If the FAAST LT-200 door is closed for a long 

time (especially at high temperatures) it may 

be necessary to use a flat-bladed screwdriver 

between the two tabs at the top of the unit to 

lever open the door (as shown above).

SAMPLING AREA

SAMPLING AREA

Whenever the FAAST LT-200 is installed outside the risk area, return 

of the exhaust air back into the protected area can reduce flow faults 

due to pressure difference.

!

MODULE MOUNT

MODULE MOUNT

F-LT-PMB 

MODULE 

MOUNT KIT 

(OPTIONAL)*

*

If required, an input/output module 

can be installed into the FAAST LT-

200 unit. The optional module mount 

kit (F-LT-PMB) will be needed for this.

IMPORTANT NOTES

1)  Do not glue the pipes into the inlets or outlets of the FAAST LT-

200 unit. 

Devices with glued pipes will be deemed as out of 

warranty because they cannot be tested

.

2)  It is recommended that the inlet and outlet connections remain 

plugged prior to use, and the outlet is temporarily sealed if the 

device is turned off during maintenance periods to prevent ingress 

of insects and spiders.

Summary of Contents for FAAST FL0111E-HS

Page 1: ...it Warning The performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Qua...

Page 2: ... place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 5 Mounting Bracket FAAST LT 200 HANGING LUGS INDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 7 8 9 10 1 11213 Minimum clearance ...

Page 3: ...es not used should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS FAAST LT MODEL INLET PIPE HOLE OUTLET P...

Page 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Page 5: ...CIFICATION MIN MAX UNITS COMMENTS Contact Rating 2 0 5 A A 30 VDC resistive load 30 VAC resistive load Life Time 105 Operations 1N6284CA FAAST LT FAAST LT C L FAAST LT R C L WARNING Switching Inductive Loads Fitting the Terminal Blocks To insert the terminal blocks into the unit use the following method 1 Insert a corner of the block into the slot see a 2 Push the length of the block into the slot...

Page 6: ...A TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 TEMPERA TURE INPUT 10b FL0122E HS 2 Channel Detector POWERING UP Using Default Settings 1 Connect a suitable 24VDC supply complying with European Standard EN 54 4 to pins 1 and 2 on terminal block T1 See Table 2 2 Check the voltage at the...

Page 7: ... INITIALIZATION ALARM PREALARM 2 10 3 1 4 5 6 7 8 9 2 10 3 1 4 5 6 7 8 9 INDICATOR ACTION WARNING OR TROUBLE COMMENT ACTION CHANNEL 1 2 ALARM ON Red Channel is in alarm relay is set No delay with default settings 1 BLINK Green when sensor is polled Not in alarm CHANNEL 1 2 PRE ALARM ON Yellow Channel is in pre alarm relay is set SMOKE LEVEL ON Yellow Led number indicates sensor alarm level reached...

Page 8: ...troduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do not work well on aspirated systems Fault Testing Simulate a fault on the detector for example block the outlet pipe and check that a fault is signalled on both the front panel of the unit and at the CIE Fire ...

Page 9: ...ernal port in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will...

Page 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Page 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Page 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Page 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Reviews: