EM-1MI Monitor Module

SPECIFICATIONS

Normal Operating Voltage: 

15 to 30 VDC

Standby Current: 

485 µA max. (continuous broadcasts); 745 µA max. avg. (continuous broadcasts, IDC Shorted)

IDC Voltage: 

5.4 VDC max.

Alarm Current: 

2.0 mA (red LED on)

Maximum IDC Wiring Resistance:  100 

Ω

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% RH Non-condensing

Dimensions: 

4.17˝ H x 4.26˝ W x 1.22˝ D; (106 mm H x 108 mm W x 31 mm D)

Accessories: 

39 k

Ω

 End of Line Resistor part #A2263-00 (included)

 

14 k

Ω

 Alarm Resistor part #A3026-000 (not included)

 

Wall cover plate (included)

 

SMB500 Surface Mount Electrical Box

BEFORE INSTALLING

This information is included as a quick reference installation 
guide. Refer to the appropriate control panel installation manual 
for detailed system information. If the modules will be installed 
in an existing operational system, inform the operator and lo-
cal authority that the system will be temporarily out of service.

NOTICE:

 This manual should be left with the owner/user of 

this equipment.

GENERAL DESCRIPTION

Monitor Module, Model EM-1MI, is used to monitor the nor-
mally open contacts of an auxiliary device. In addition to mon-
itoring the contact, the device will monitor the wiring to the 
device for open circuits via an end of line resistor. The module 
also has on-board short circuit isolators to prevent shorts on 
the signaling line circuit from disabling more than one device 
on  the  intelligent  loop.  This  device  is  capable  of  Class  A  or 
Class B operation.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to 
a listed compatible control panel.

MOUNTING

The module mounts directly to 4˝ square electrical boxes. The 
box must have a minimum depth of 2

1

/

8

˝. Modules must be 

mounted with the arrow facing upward for proper operation 
of the IR programming tool. Surface mounted electrical boxes 
(SMB500) are available from System Sensor.

WIRING

NOTE:

 All wiring must conform to applicable local codes, or-

dinances, and regulations. 
1.   Install module wiring in accordance with the job drawings 

and appropriate wiring diagrams.

2.   For new installations use the enclosed 39 

k

Ω EOL resistor. 

For retrofit applications where the existing 47 k

Ω

 cannot 

be easily replaced, it may be left in place without loss of 
performance.

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3.   Set the address on the module per job drawings using the 

IR configuration tool (model no. EA-CT).

4.  Secure module to electrical box (supplied by installer). 

AUTO ADDRESSING

Eclipse Series devices are capable of supporting auto address-
ing, if the fire alarm control panel is designed to do so. In auto 
addressing, the control panel, through the use of each device’s 
on-board isolators, can automatically assign device addresses. 
In order to control which devices are addressed first in wiring 
configurations with branches, a branch marker can be set at a 
particular device. A branch marker is an electronic value from 
0 to 255 stored in the device memory. The branch markers are 
set with the IR configuration tool, EA-CT. 

TERMINAL DEFINITIONS

T1 

(+) SLC in/out  T7 

(–) IDC Class A/B

T2 

(–) SLC in/out  T8 

(+) IDC Class A/B

T3 

(+) SLC in/out   T9 

(+) IDC Class A

T4 

(–) SLC in/out   T10 

(–) IDC Class A

FIGURE 1. MONITOR MODULE:

LED INDICATOR

IR RECEIVER

C0102-00

I56-2

022-00

3