System Sensor CZ-6 Installation And Maintenance Instructions Download Page 1

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 
the appropriate control panel installation manual for detailed system informa-
tion. If the modules will be installed in an existing operational system, inform 
the operator and local authority that the system will be temporarily out of ser-
vice. Disconnect the power to the control panel before installing the modules. 
This system contains static sensitive components. Always ground yourself 
with a proper wrist strap before handling any circuits so that static charges are 
removed from the body. The module housing should also be grounded.

NOTICE: This manual should be left with the owner/user of this equipment. 

GENERAL DESCRIPTION

The CZ-6 Six Zone Interface Module is intended for use in an intelligent alarm 
system. Each module provides an interface between the intelligent alarm sys-
tem and a conventional alarm system loop. A common SLC input is used 
for all modules, and the initiating device loops share a common supervisory 
supply and ground. Otherwise, each monitor operates independently from the 
others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first module 
from 01 to 94. The remaining modules are automatically assigned to the next 
five higher addresses. Provisions are included for disabling a maximum of two 
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the 
LEDs to blink, latch on, or latch off.

Included: 

(5) 1 x 4 Terminal Blocks            (2) 11/4” Stand offs           (3) Shunts

 

  

(4) Machine Screws           (2) Nuts          (1) Long Power Supply Jumper

(6) 3.9k Ohm 

End of Line Resistors

Shipped on Board:

(2) Shunts in Class A/B position

(Shipped in Class B position, remove shunts for Class A)

INSTALLATION AND MAINTENANCE INSTRUCTIONS

CZ-6 Six Zone Interface Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2.3 mA @ 24V

Alarm Current: 

40 mA (assumes all six LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H x 5.8˝W x 1.25˝D

Accessories: 

CH-6 Chassis; BB-2 Cabinet; BB-6 Cabinet

Wire Gauge: 

12-18 AWG

Maximum IDC Wiring Resistance: 

25 Ohms

External Power Supply Voltage: 

Regulated 24VDC

Ripple Voltage: 

0.1 volts RMS maximum

IDC (supervised and power limited)
     DC Voltage: 

18-28 volts power limited

     Frequency: 

DC

Current: 

90mA per circuit

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
system control panel. Contact System Sensor for a list of compatible detectors.  

COMPONENTS

Following are descriptions of the CZ-6 mounting frameworks. There are two 
mounting options for CZ-6 modules:

•  Up to six CZ-6 modules can be installed on a CH-6 in a BB-6 cabinet

•  One or two CZ-6 modules can be installed in a BB-2 cabinet

Chassis

 

The CH-6 chassis is used to mount CZ-6 modules in a BB-6, cabinet. It accom-
modates up to six CZ-6 modules in a single cabinet row three modules wide 
and two modules deep.

FIGURE 1. CH-6 CHASSIS:

The BB-2 cabinet has a built-in chassis that will accommodate one or two 
CZ-6 modules.

FIGURE 2: BB-2 CABINET

0

1

2 3 4 5 6

7

8

9

0

7

8

65

4

3

2

1

9

10

11

12

13

14

15

BA

SE

 A

D

D

R

ES

S

AD

D

R

ES

S

D

IS

AB

LE

NO

NE

ON

E

TW

O

THR

EE

0

1

2 3 4 5 6

7

8

9

0

7

8

65

4

3

2

1

9

10

11

12

13

14

15

BA

SE

 A

DDRE

SS

ADD
R

ES

S

DI

SA

BL

E

NONE

ON

E

TW

O

THR

EE

I56-1799-009

C0202-00

C0206-00

C0234-00

  

I56-1799-009 

 

 03-11