B401BR750 Plug-in Detector Base

For use with the following smoke detectors:
1451, 2451, and 2451TH

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor manual I56-407,

Guide for Proper Use of System Smoke Detectors

, which

provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
(For installations in Canada, refer to CAN4-S524, 

Standard

for the Installation of Fire Alarm Systems

, and CEC Part 1,

Sec. 32.)

NOTICE:

 This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

The detector used with this base must be

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications

Base Diameter:

6.2 inches (157 mm)

Base Height:

1.1 inches (29 mm)

Weight:

0.3 lb. (130 g)

Mounting:

4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch octagon box. Min. Depth–1.5 inches

Operating Temperature Range:

0

°

 to +49

°

C (32

°

 to 120

°

F)

Operating Humidity Range:

10% to 93% Relative Humidity, noncondensing

Electrical Ratings — includes base and detector

System Voltage:

12/24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 

µ

F Maximum

Standby Ratings:

17 VDC Minimum; 32 VDC Maximum
120 

µ

A Maximum

Alarm Ratings:

10mA Minimum at 13.5 VDC; 39mA Maximum at 32 VDC
(If used, the RA400 remote lamp operates within specified detector alarm currents.)

Reset Voltage:

2.5 VDC Minimum

Reset Time:

0.3 Seconds Maximum

Start-up Time:

34.0 Seconds Maximum

General Description

The B401BR750 plug-in detector base is used with System
Sensor model 2451 and 2451TH photoelectronic detector
heads and model 1451A  ionization detector heads. The ca-
pability of plugging these detectors into a variety of special
bases makes them more versatile than equivalent direct-
wired models. Refer to the System Sensor catalog for other
available plug-in detector bases.

This base is intended for use in 2-wire systems, with screw
terminals provided for power, ground, and remote annun-
ciator connections. It also contains a resistor to provide
current limiting in the alarm state.