System Sensor B200SR-LF Installation And Maintenance Instructions Download Page 1

B200SR-LF 

Low Frequency Intelligent Sounder Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING

Read System Sensor’s 

Applications Guide for System Smoke Detectors 

(SPAG91), which provides detailed information on sensor spacing, placement, 
zoning, wiring, and special applications. This manual is available online at 
www.systemsensor.com. NFPA 72 and NEMA guidelines should be observed. 
The National Fire Alarm Code, NFPA 72, requires effective January 1, 2014, 
that audible appliances installed in sleeping areas produce a low frequency 
alarm signal that shall be a square wave or provide equivalent awakening abil-
ity with a fundamental frequency of 520 Hz +/– 10%.

NOTICE

: This manual should be left with the owner/user of this equipment.

IMPORTANT

: The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector should be cleaned at 
least once a year.

GENERAL DESCRIPTION

The B200SR-LF low frequency sounder base is used with System Sensor 200-Se-
ries sensor heads or equivalent. For a list of compatible sensors, refer to the Sys-
tem Sensor website at www.systemsensor.com. Refer to the appropriate manual 
for more information on sensors.

The B200SR-LF low frequency sounder base generates a low frequency tone 
around 520 Hz.  Studies have shown that low frequency audible devices that 
operate around 520 Hz are more effective in waking individuals in sleeping 
areas. It offers maximum flexibility in configuration and operation to meet or 
exceed the requirements of UL268 and UL464.

The sounder base is capable of producing either the distinctive three-pulse 
temporal pattern (ANSI Temporal 3) fire alarm signal now required by NFPA 
72 for commercial and residential applications or a continuous tone by simply 
removing the included jumper from the device.  Additionally, the B200SR-LF 
is designed to be compatible with existing installations of B501-Series sounder 
bases.

The sounder base is intended for use with intelligent systems. The sounder 
base requires an external 24 VDC power supply. The connections for the 
external power supply and the communication loop are isolated to prevent 
electrical interaction between them. Refer to the panel manual for maximum 
allowable number of units per loop.

NOTE

: For NFPA72 Installations, the Temporal 3 tone should be used for public 

mode evacuation.

NOTE

: When not used as a supplementary evacuation system, the external 24 

VDC supply shall be treated as a component of the main power supply system 
and shall fall under the requirements of the main power supply system per 
NFPA 72.

SPECIFICATIONS

Base Diameter: 

6.875” (17.46 cm)

Base Height (less sensor): 

2.0” (5.08 cm)

Weight: 

0.6 lb. (272 gm)

Operating Temperature Range: 

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com

Operating Humidity Range: 

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings

External Supply Voltage: 

16 to 33 VDC (VFWR)

Standby Current: 

1mA maximum VDC

Alarm Current: 

65 mA maximum @ 33.0 VDC

 

90 mA maximum @ 24.0 VDC

 

125 mA maximum @16.0 VDC

SLC Electrical Ratings

SLC Operating Voltage: 

15 to 32 VDC

SLC Standby Current: 

Refer to applicable sensor specification

Sound Output

 

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

WIRING GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction and must not be of such length or wire 
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and 
accessory devices should be color coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from responding properly 
in the event of a fire.

Wire sizes up to 12 AWG (2.5 mm

2

) may be used with the base. The sounder 

base will be shipped with the screw terminals set for 14 AWG wiring. If 12 
AWG wire is to be used, back out the screws to allow the wire to fit beneath 
the clamping plates. For best system performance, the power (+ and -) wires 
and the communication circuit wires should be twisted pair or shielded cable 
installed in a separate grounded conduit to protect the communication loop 
from electrical interference.

Make wire connections by stripping about 3/8” of insulation from the end of 
the wire. Then, slide the bare end of the wire under the appropriate clamping 
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the 
wire under the clamping plate (See Figure 2) The wiring diagram for a typical 
2-wire intelligent system is shown in Figure 4.

CAUTION

For system monitoring - for terminals 4 and 5, do not use looped wire under termi-
nals.  Break wire run as shown in Figure 2 to provide monitoring of connections.

B200SR-LF TERMINALS

No. Function
1.  Not Used
2.  Positive (+) Comm. Line In and Out
3.  Negative (-) Comm. Line In and Out
4.  External Supply Positive (+)
5.  External Supply Negative (-)
6.  Sounder Base Interconnect  

I56-4

152-00

3R

  

I56-4152-003R 

 

 06-10