B114LPBT Plug-in Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

SPECIFICATIONS

Base Diameter: 

6.2 in (15.7 cm)

Base Height: 

1.1 in (2.9cm)

Weight: 

0.6 lb (260 g)

Mounting: 

4˝ square box without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;

 3

1

2

˝ octagon box, minimum depth 1.5˝

Operating Temperature Range: 

0°C to 49°C (32°F to 120°F)

Operating Humidity Range: 

10% to 93% Relative Humidity

Electrical Ratings (includes base and detector)

System Voltage: 

24 VAC/DC, 60 Hz

Relay Contact Ratings Resistive Load: Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC
 

(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)

Standby Current: 

25 mA typical @ 24V AC/DC; 35 mA maximum @ 35V AC/DC

Alarm Current: 

75 mA typical @ 24V AC/DC; 94 mA maximum @ 35V AC/DC

Start-up Time (after 60 second reset): 36.0 Seconds maximum

BEFORE INSTALLING 

Please read thoroughly System Sensor’s 

Applications Guide for System Smoke 

Detectors

 (SPAG91), which provides detailed information on detector spacing, 

placement, zoning, wiring, and special applications. This is available online 
from System Sensor’s web site: www.systemsensor.com.

NOTICE:

 This manual should be left with the owner/user of this equipment.

IMPORTANT:

 The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector used with this base 
should be cleaned at least once a year.

GENERAL DESCRIPTION

The B114LPBT detector base is designed for use with System Sensor model 
2151 photoelectronic and 1151 ionization detector heads. The capability of 
plugging these detectors into a variety of special bases makes them more ver-
satile than equivalent direct-wired models. Refer to the System Sensor catalog 
for other available plug-in bases. The B114LPBT base is intended for use in 
4-wire systems with terminals provided for remote annunciator and relay con-
nections. 

MOUNTING

The detector base mounts directly to 3

1

/

2

- and 4-inch octagon boxes and 

4-inch square boxes. To mount the base, remove the decorative ring by rotat-
ing it in either direction to unhook the snaps before separating the ring from 
the base. Use the screws supplied with the junction box to attach the base to 
the box through the appropriate mounting slots in the base. 

Position the decorative ring around the base and rotate it in either direction 
until the ring snaps into place (see Figure 2). 

BASE TERMINALS

NO.

FUNCTION

NO.

FUNCTION

1

Remote Annunciator (+)

8

N.O.

Alarm Relay

2

Test Coil (+)

9

N.O.

Form A

3

Not Used

10

C.

Initiation

4

Remote Annunciator (–)

11

C.

Contacts

5

RTC (–)

12

N.O.

Alarm Relay

6

C.

Supervisory Relay

13

N.C.

Form C

7

N.O.

Form A Contacts

14

C.

Auxiliary Contacts

INSTALLATION GUIDELINES

All wiring must be installed in compliance with the National Electrical Code,  
all applicable local codes, and any special requirements of the authority hav-
ing jurisdiction, using the proper wire size. The conductors used to connect 
smoke detectors to control panels and accessory devices should be color-
coded to reduce the likelihood of wiring errors. Improper connections can 
prevent a system from responding properly in the event of a fire.

For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than 16 gauge (1.5 square mm), and that 

two- or three-conductor wire be no smaller than 18 gauge (1.0 square mm). 
For best performance, alarm loop conductors should be installed in separate 
grounded conduit or shielded cable to protect the alarm loop from extraneous 
electrical interference.

Smoke detectors and alarm systems control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular model control 
panel being used before wiring the detector loops.

FIGURE 1. BASE TERMINALS:

BASE 

TERMINALS

SHORTING 

SPRING

STRIP GAUGE

1

2

3

5

4

TAMPER 

RESISTANT TAB

6

7

8

9

10

11

12

13 14

24VDC/24VAC 

TERMINALS

C1025-00

FIGURE 2. MOUNTING BASE TO BOX:

SNAP ON 

DECORATIVE 

RING

SCREWS 

(NOT SUPPLIED)

DETECTOR 

BASE

BOX

(NOT SUPPLIED)

SHORTING 

SPRING

C0503-00

I56-2

169-00

2R

For use with the following smoke detectors: 

US

 - 1151, 2151, 2151T; 

CANADA

 - 1151A, 2151A, 2151TA; 

EUROPE

 - 1151E, 2151E

  

I56-2169-002R 

 