background image

B110LP Plug-in Detector Base

For use with the following smoke detectors:

IN US: 

 

1151, 2151

IN CANADA: 

1151A, 2151A

IN EUROPE: 

1151E, 2151E

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING 

Please thoroughly read the 

System Smoke Detectors Application Guide

, which 

provides detailed information on detector spacing, placement, zoning, wiring, and 

special applications. Copies of this manual are available at no charge from System 

Sensor. (For installation in Canada, please refer to CAN/ULC-S524, 

Standard for the 

Installation of Fire Alarm Systems

 and CEC Part 1, Sec. 32.)

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: The detector used with this base must be tested and maintained regu-

larly following NFPA 72 requirements. The detector used with this base should be 

cleaned at least once a year.

GENERAL DESCRIPTION

The Model B110LP detector base is designed for use with System Sensor models 

2151 photoelectronic and 1151 ionization detector heads. This two-wire base is 

equipped with screw terminals for the connection of power, ground, and an optional 

remote annunciator.

MOUNTING

The detector base mounts directly to 3-½ inch and 4-inch octagon boxes and 4-inch 

square boxes, with or without plaster rings. To mount the base, remove the decorative 

ring by rotating it in either direction to unhook the snaps before separating the ring 

from the base. Use the screws supplied with the junction box to attach the base to the 

box through the appropriate slots in the base (see Figure 1). Position the decorative 

ring around the base and rotate it in either direction until the ring snaps into place. 

INSTALLATION GUIDELINES

Allowable loop resistance is an important specification for control panels as well as 

for smoke detectors and their bases. The alarm system cannot be expected to oper-

ate correctly if system components have incompatible allowable loop resistances. 

Therefore, before beginning installation, refer to the control panel manufacturer’s 

loop resistance specification to ensure that it is listed as compatible with the System 

Sensor base and smoke detector being installed.
System Sensor smoke detectors and mounting bases are marked with a compatibility 

identifier as the last digit of a five-digit code stamped on the back of the product. 

Connect detectors only to compatible control units as indicated in System Sensor’s 

compatibility chart. This chart consists of a current list of UL-listed control unit/

detector combinations and is available from System Sensor upon request.
All wiring must be installed in compliance with the National Electrical Code and all 

applicable local codes and any special requirements of the authority having jurisdic-

SPECIFICATIONS

Base Diameter: 

6.2 inches (157 mm)

Base Height: 

0.95 inches (24 mm)

Weight: 

0.3 lb. (137 g)

Mounting: 

4-inch square box with or without plaster ring. Min. depth–1.5 inches

 

3-1/2-inch octagon box. Min. depth–1.5 inches

Operating Temperature Range: 

0° to 49°C (32° to 120°F)

Operating Humidity Range: 

10% to 93% Relative Humidity, Noncondensing 

Electrical Ratings - includes base and detector

System Voltage: 

12/24 VDC

Maximum Ripple Voltage: 

4 Volts peak-to-peak

Start-up Capacitance: 

0.02 µF Maximum

Standby Ratings: 

8.5 VDC Minimum

 

35 VDC Maximum

 

120 µA Maximum

Alarm Ratings: 

4.2 VDC Minimum at 10 mA

 

6.6 VDC Maximum at 100 mA

  

(Alarm current must be limited to 100 mA (130 mA for models 1151 and 2151) by the control panel. If it is used, the RA400Z 

Remote Annunciator operates within the specified detector alarm currents.)

Reset Voltage: 

2.5 VDC Minimum

Reset Time: 

0.3 Seconds Minimum

Start-up Time: 

34.0 Seconds Maximum

I56-0594-005R

SNAP ON 

DECORATIVE 

RING

SCREWS 

(NOT SUPPLIED)

DETECTOR 

BASE

BOX

(NOT SUPPLIED)

SHORTING 

SPRING

FIGURE 1. MOUNTING BASE TO BOX:

C0503-00

  

I56-0594-005R 

 

 04-21

Reviews: