APA151 Annunciator
with Piezo Alert

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: 

These models were only tested at the 16-33 Volt 

DC limits. This does not include the 80% low-end or 110% 
high-end voltage limits. This manual shall be left with the 
owner/user of this equipment.

General Information

The National Fire Protection Association (NFPA) has pub-
lished codes, standards, and recommended practices for the 
installation and use of this product. It is recommended that 
the installer be familiar with these requirements, with local 
codes, and any special requirements of the local authority 
having jurisdiction. For further information, consult NFPA 
72 and 90A requirements.
The  System  Sensor  APA151  annunciator  with  piezo  alert 
is  an  audible  signal  appliance  for  fire  alarm  service.  It  is 
intended for use in System Sensor 4-wire conventional duct 
smoke detector applications without a system control panel 
to comply with NFPA 90A. 
The APA151 provides a red alarm LED, with an audible an-
nunciation of an alarm signal, and a green power LED.

Specifications

Dimensions: 

4.6˝ L × 2.9˝ W × .45˝ D

Weight: 

.17 lbs.

Electrical Requirements: 
 

Voltage: 

Regulated 24VDC

 

Operational Voltage: 

16–33 VDC

 

Maximum Operating Current: 

30mA

Connections: 

#6 binding head screws, 12 AWG to 18 AWG wire

UL Reverberant Room: 

81 dBA min. @ 10 ft.

Standard Operating Temperature: 

0°C to 49°C (32°F to 120°F)

Humidity Range: 

10% to 93% non-condensing