1412B and 1424 Direct Wire 
Ionization Smoke Detectors

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing 

Please  thoroughly  read  the  System  Sensor  manual  A05-
1003, 

Applications  Guide  for  System  Smoke  Detectors

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  at  no  charge  from  System 
Sensor.  (For  installation  in  Canada,  refer  to  CAN/ULC-
S524, 

Standard  for  the  Installation  of  Fire  Alarm  Systems

 

and CEC Part 1, Sec. 32.)

General Description

System  Sensor  1412  and  1424  dual-chamber  ionization 
smoke  detectors  utilize  state-of-the-art,  unipolar  sensing 
chambers.  These  detectors  are  designed  to  provide  open 
area protection, and to be used with UL-listed 4-wire con-
trol panels. The 1412 for 12 volt panels operates at 12VDC, 
and  the  1424  for  24  volt  panels  operates  at  24VDC.  The 
detectors’ operation and sensitivity can be tested in place. 
These detectors are listed to UL 268 and are latching type 
system  detectors.  When  latched  in  alarm,  the  detectors 
must be reset by a momentary power interruption.

Specifications

Diameter:                                           5.5 inches (14 cm)
Height:                                              3.12 inches (8.0 cm)
Weight:                                              0.7 lb (310 gm)
Operating Temperature:                      0°C to +49°C (32°F to 120°F)
Operating Humidity:                           10% to 93% Relative Humidity Non-condensing
Locking Alarm:                                  Reset by momentary power interruption.

Relay Contact Ratings

Resistive or Inductive (60% power factor) load
Form A:                                             2.0A @ 30VAC/DC
Form C:*                                            0.6A @ 110VDC, 2.0A @ 30VDC
                                                         1.0A @ 125VAC, 2.0A @ 30VAC
*For Canadian installations, relay contact rating is 2.0A @ 30VAC/DC
Electrical Ratings:                                    1412                              1424
System Voltage:                                        12                                 24                           DC (4V Maximum Ripple)
Supply Voltages:                                      11.3                                20                           VDC Minimum
                                                              17.3                                29                           VDC Maximum
Reset Voltages:                                         .73                                 .8                           VDC Minimum
Standby Current:                                     100                                100                         

µ

A Maximum

Alarm Currents:                                      35.2                              21.3                          mA Minimum
                                                              77.0                              40.6                          mA Maximum
The alarm and auxiliary relay operate within the specified voltage ratings.
Reset Time:                                              0.3                                0.3                           Seconds
Start-up Time:                                          30                                  30                           Seconds

An LED on the detector provides a local indication of the 
detector’s  status.  If  power  is  applied  to  the  detector,  and 
the detector is functioning properly in standby, the status 
LED will blink every 10 seconds. In alarm, the LED will be 
latched on continuously until the detector is reset.

Each detector contains one Form A (SPST-NO) contact for 
connection  to  the  alarm-initiating  circuit,  and  one  Form 
C  (SPDT-NO/NC)  set  of  auxiliary  contacts.  Supervision 
of  detector  power  is  accomplished  by  installing  a  Power 
Supervisory End-of-Line Relay Module (A77-716) at the end 
of the detector power loop. When power is applied to and 
through the detectors, the EOL Power Supervisory Module 
is energized. Its relay contacts close and provide a closed 
series circuit in the control panel’s alarm-initiating loop. A 
power failure or a break in the detector power loop de-ener-
gizes the EOL Module. The relay contacts open and trigger 
a trouble signal at the control panel.

Summary of Contents for 1424

Page 1: ...condensing Locking Alarm Reset by momentary power interruption Relay Contact Ratings Resistive or Inductive 60 power factor load Form A 2 0A 30VAC DC Form C 0 6A 110VDC 2 0A 30VDC 1 0A 125VAC 2 0A 30VAC For Canadian installations relay contact rating is 2 0A 30VAC DC Electrical Ratings 1412 1424 System Voltage 12 24 DC 4V Maximum Ripple Supply Voltages 11 3 20 VDC Minimum 17 3 29 VDC Maximum Reset...

Page 2: ...nd by mode and will transfer in alarm condition CAUTION For system supervision for terminals 1 2 7 and 8 do not use looped wire under terminals Break wire run to provide system supervision of connections For signal wiring the wiring between interconnected detectors it is recommended that the wire be no smaller than 18 gauge Wire sizes up to 12 gauge wire may be used For best system performance the...

Page 3: ...ce CAUTION Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose Testing NOTE Before testing notify the proper authorities that the smoke detector system is undergoing main tenance and therefore will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms Before testin...

Page 4: ...mbly by depressing the three lock prongs on the top of the cover rotate the cover counterclockwise and pull the screen and cover assembly away from the detector see Figure 5 Usage of System Sensor CRT400 cover removal tool is recommended 2 Remove the screen from the cover 3 Use a vacuum cleaner to remove dust from the screen the cover and the sensing chamber 4 After cleaning snap the screen into t...

Reviews: