1251B Plug-in Intelligent Ionization 
Sensor with Communications

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing 

This sensor must be installed in compliance with the con-
trol panel system installation manual. The installation must 
meet the requirements of the Authority Having Jurisdiction 
(AHJ). Sensors offer maximum performance when installed 
in compliance with the National Fire Protection Association 
(NFPA); see NFPA 72. 

General Description

Model  1251B  intelligent  ionization  sensor  uses  a  state-of-
the-art  sensing  chamber.  These  sensors  are  designed  to 
provide open area protection and are intended for use with 
compatible control panels only.

Two LEDs on each sensor light to provide a local, visible 
sensor  indication.  Remote  LED  annunciator  capability  is 
also available as an optional accessory (RA400Z).

The 1251B requires compatible addressable communica-
tions to function properly. Connect this sensor to listed-
compatible control panels only.

Spacing

System Sensor recommends spacing sensors in compliance 
with  NFPA  72.  In  low  air  flow  applications  with  smooth 
ceilings,  space  sensors  30  feet  apart.  For  specific  infor-
mation  regarding  sensor  spacing,  placement,  and  special 
applications, refer to NFPA 72 or the 

System Smoke Detector 

Application Guide,

 available from System Sensor.

Wiring Guide

All  wiring  must  be  installed  in  compliance  with  the 
National  Electrical  Code,  applicable  local  codes,  and  any 
special requirements of the Authority Having Jurisdiction. 

Specifications

Operating Voltage Range:  

15 to 32 VDC

Max. Avg. Standby Current: 

300

µ

A

 

@ 24 VDC (one

 

communication every 5 sec. with LED blink enabled)

Max. Alarm Current (LED on): 

6.5 mA @ 24 VDC

Operating Humidity Range: 

10% to 93% Relative Humidity, non condensing

Operating Temperature Range: 

0°C to 49°C (32°F to 120°F)

Height:  

2.0 inches (51 mm) installed in B210LP Base

Diameter: 

6.1 inches (155 mm) installed in B210LP Base

 

4.1 inches (104 mm) installed in B501 Base

Weight:    

5.4 oz. (153 g)

Proper wire gauges should be used. The installation wires 
should  be  color-coded  to  limit  wiring  mistakes  and  ease 
system troubleshooting. Improper connections will prevent 
a system from responding properly in the event of a fire.

Remove  power  from  the  communication  line  before 
installing sensors.

1. Wire the sensor base (supplied separately) per the wir-

ing diagram, see Figure 1.

2. Set the desired address on the sensor address switches, 

see Figure 2.

3. Install the sensor into the sensor base. Push the sensor 

into the base while turning it clockwise to secure it in 
place.

4. After all sensors have been installed, apply power to the 

control unit and activate the communication line.

5. Test the sensor(s) as described in the TESTING section 

of this manual.

CAUTION

Dust covers provide limited protection against airborne dust 
particles  during  shipping.  Dust  covers  must  be  removed 
before the sensors can sense smoke. Remove sensors prior 
to heavy remodeling or construction.

Tamper-Resistance

Model  1251B  includes  a  tamper-resistant  capability  that 
prevents their removal from the bracket without the use of 
a tool. Refer to the base manual for details on making use 
of this capability.