background image

D200-63-00

1

I56-931-06

1112/24D Ionization Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read System Sensor Manual I56-407,

Guide for Proper Use of System Smoke Detectors,

  which

provides detailed information on detector spacing,
placement, zoning, wiring, and special applications.
Copies of this manual are available at no charge from
System Sensor.

NOTICE: 

This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

This detector must be tested and maintained

following NFPA 72 requirements. The detector should be
cleaned at least once a year.

General Description

The 1112/24D is a 4-wire ionization smoke detector that
uses a state-of-the-art sensing chamber. This detector is
designed to provide open area protection.

Installation of this detector is simplified by the use of an
adapter bracket and a plug-in screw terminal block that
can be prewired to the system, allowing the detector to
be easily installed or removed for cleaning. The detector
sensitivity can be tested in place using the MOD400R
Test Module.

An LED on the detector provides local visual indication of
the detector status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every five seconds. The LED also latches on in alarm.

The 1112/24D also features visual indication that mainte-
nance is required; if the sensing chamber drifts out of its
sensitivity limits, the LED ceases to blink.

IMPORTANT: OBSERVE POLARITY

This detector requires that you observe polarity when wiring. If wiring polarity is not observed on the

initiating loop, the unit will send an alarm signal to the control panel to signify incorrect wiring.

A78-2336-05

OPTIONAL CLASS A WIRING

EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716B 12/24V

POWER

TO

DETECTORS

UL LISTED

CONTROL

PANEL

INITIATING

LOOP

+

+

+

+

+

+

N.O.

C

+

+

N.O.

C

: Observe polarity in power and initiating loops when wiring.

NOTE

Figure 1. Wiring diagram for the 1112/24D detector:

Summary of Contents for 1112/24D

Page 1: ...w terminal block that can be prewired to the system allowing the detector to be easily installed or removed for cleaning The detector sensitivity can be tested in place using the MOD400R Test Module An LED on the detector provides local visual indication of the detector status If power is applied to the detector and it is functioning normally in standby the status LED blinks every five seconds The...

Page 2: ...ol panels have specifications for allowable loop resistance Consult the control panel specifications for the total loop resistance al lowed for the control panel being used before wiring the detector loops Wire connections are made by stripping about 1 4 inch of insulation from the end of the feed wire inserting the wire into the appropriate terminal and tightening the screw to secure the wire in ...

Page 3: ...struction as part of returning the system to service A78 2564 01A Figure 4 Top and side views showing location of test switch PUSH RECESSED SWITCH WITH A 0 18 MAX DIAMETER TOOL A78 2564 00C I N T A P T O N O D LED TEST MODULE SOCKET RECESSED TEST SWITCH Testing NOTE Before testing notify the proper authorities that the smoke detector system is undergoing mainte nance and therefore will be temporar...

Page 4: ...toelectric detectors are required to pass fire tests of the flaming and smoldering type This is to ensure that both can detect a wide range of types of fires Ionization detectors offer a broad range of fire sensing capa bility but they are somewhat better at detecting fast flaming fires than slow smoldering fires Photoelectric detectors sense smoldering fires better than flaming fires which have l...

Reviews: