Section VI
Control Interface Details
006-0007068 UPS-1500-S-2S Guide
Rev E
51 of 60
09/10/20
Ethernet Interface
The Ethernet interface provides a web page based user interface for monitoring and control
of the UPS. The user can configure email alerts for UPS alarm conditions. The interface also
exposes an SNMP interface compliant to RFC-1628.
The Ethernet interface supports 10BASE-T and 100BASE-T standards. It utilizes a standard RJ-
45 connector, also allowing a metallic sealable circular military outer housing. The interface
supports auto-negotiation, polarity correction, and Auto-MDIX (detection and use of straight
through or cross-over cables).
IP address assignment can be done via DHCP or user entry of a static address. The interface also
supports a direct connection between the UPS and a host computer by including a DHCP server
internal to the UPS.
For a detailed description of the Ethernet port and SNMP implementation see the SynQor website
at:
http://www.synqor.com/ups/documents/UPS_Ethernet_SNMP_UG.pdf