1
Command Line
To display the current settings, enter:
F74<CR>
XLi responds, using the following format:
F74<S><CLK SOURCE><CR><LF>
where:
For example, enter:
F74<CR>
XLi responds (example):
F74 PRI<CR><LF>
To select PRI-SEC-SEC as the new clock source/fail-over pattern, enter:
F74 PRI-SEC-SEC<CR>
XLi responds:
OK<CR><LF >
F90 – Code Output Configuration
Use function F90 to configure the time code output format (IRIG-A, IRIG-B, or NASA 36) and modulation
type (AM or DC) on the XLi’s standard CODE output.
F
= ASCII character F.
74
= function
number.
<S>
= Space
<CLK SOURCE>
= Clock
Source:
•
PRI
•
SEC
•
PRI-SEC-SEC
•
PRI-SEC-PRI
•
PRI-NSEC-PRI
<CR>
= carriage return character.
<LF>
= line feed character.