3
5
Slide the longer bolt of the lightning suppressor through the D-hole, and attach with a nut
and a washer (provided).
6
Install 3.8 cm nonmetallic conduit from the antenna to the lightning suppressor, and from
the lightning suppressor to the cable entrance into the building
7
Install a user-supplied bracket, preferably non-metallic, to support the vertical section of
conduit to the antenna.
8
Connect a cable to the antenna, route the cable through the conduit, and connect the
cable to the lightning suppressor.
9
Connect a cable to the lightning suppressor, route the cable through the conduit into the
building, and route the cable through the building to the TimeSource 3100 Shelf location.
10
If the lightning suppressor was not mounted directly to a valid earth ground, crimp a length
of 4.115 mm (6 AWG) round cable to the two-hole terminal, slide the terminal over two of
the three threaded posts on the lightning suppressor mounting plate, and attach the
terminal to the mounting plate with two KEPS nuts. Use the two posts that allow the least
bending of the 4.115 mm (6 AWG) ground cable.
11
Attach the other end of the cable to a valid earth ground.
12
Install fire-stopping material in all holes opened in the roof and/or walls during this
procedure.
Procedure B.
Antenna Mounting and Cable Connection (cont’d)
Step
Procedure
Summary of Contents for TimeSource 3100
Page 1: ...TimeSource 3100 GPS Primary Reference Source 097 72020 01 Issue 9 November 2003 ...
Page 49: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Page 109: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Page 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...