260 TimeHub 5500 User’s Guide
097-55501-01 Revision M – January 2009
Chapter 5 Maintaining the TimeHub 5500
Upgrading the Software
Upgrading the TimeHub NTP Firmware
Use this procedure to upgrade the firmware in the NTP Server card from Release
2.0.6 to 2.0.x. Do not use this procedure to upgrade the firmware from Release 1.x.x
to any later version.
Required Equipment
A computer with FTP/SFTP support and a LAN connection. This computer is
used as an FTP server.
A computer with ProComm Plus, HyperTerminal, or other communications
software
CD with TimeHub NTP Release 2.0.x firmware image
Load the firmware image file
thntp-2.x.x-1.x86_586.rpm
onto the FTP server.
Procedure
1. Ensure that the Management port of the rear NTP Connector module is
connected and configured to a LAN. See
Making Communication Connections
on page 122 for details.
2. Connect to the TimeHub using the procedure in
3. Issue the
RTRV-NETYPE-ALL:::ctag;
TL1 command to check the version
information and hardware setup of the NTP cards to be upgraded.
4. Issue the following TL1 command to start the firmware download process on the
Standby NTP Server card:
LOAD-PROGRAM::Sa-OUTnb:<ctag>::"<filename>","<ftp-server>",
"<user>","<password>";
for example:
LOAD-PROGRAM::S0-OUT4B:user1::"thntp-2.0.6p-1.x86_586.rpm","
ftp/192,168.5.11","user","password";
where:
–
S0-OUT4B
is the <aid> of the standby NTP card to be upgraded
–
user1
is the <ctag>
–
"thntp-2.0.6p-1.x86_586.rpm"
is the absolute path and file name of
the image file on the FTP server
–
"ftp/192,168.5.11"
is the Ethernet address of the FTP server
–
"user"
is the user name for the FTP server
–
"password"
is the user’s password for the FTP server