234 TimeHub 5500 User’s Guide
097-55501-01 Revision M – January 2009
Chapter 5 Maintaining the TimeHub 5500
Troubleshooting the TimeHub 5500
Table 5-5. Troubleshooting the 5 MHz Output Driver Card
Name
State
Description
Action
Power
Off
Power is not present.
1. If all LEDs on the system are off,
apply power or troubleshoot the -48 V
power source.2. If all LEDs on the
Output Driver card are off, replace the
card.
Green
Power is Present.
None Required.
Fuse
Off
The Output Driver card fuse is
not open.
None Required.
Red
The Output Driver card fuse is
open.
1. Remove the module and replace
the 1 amp GMP fuse (F1). 2. If the
replacement fuse fails, replace the
card.
Alarm
Off
There is no alarm condition.
None Required.
Red
An alarm condition exists.
If the Fail LED is also lit, replace the
card. If not, check the alarm
messages to determine the cause of
the failure. Refer to the TL1
Reference Guide for details on error
messages. Reasons the Alarm LED
could be lit:1.
Fail
Off
No hardware or firmware
failure has occurred on the
Output Driver card.
None Required.
Red
A hardware or firmware
failure has occurred on the
Output Driver card.
The Fail LED could be lit for the
following reasons:1.
Port On
Ch 1– 4
Off
Port is disabled.
Enable port if output is needed.
Green
Port is enabled.
None Required.