Chapter 6 Alarms and Events
Communication Module Alarms and Events
272
SSU-2000e Technical Reference
12713140-003-2 Revision E.01 – January 2007
Table 6-6. Basic +SNMPv2 and Basic +NTP + SNMPv2 Communications Module Alarm and Event Messages
Alarm/
Event/
Trap ID
Typical Alarm/Event/Trap
Response
Description/
Corrective Action
000
Communication, Fault
Unable to communicate with other modules. Re-seat modules.
001
InterCommunication, Fault
Identifies master output controller. No action necessary.
002
Power-A, Lost
Verify that the fuse for Power A is properly installed and not OPEN.
Verify that Power Bus A is providing –48 VDC to the unit. If no
power is connected to the Power A input and there is no plan to
connect power, issue the command
AL 10-1 IG
at the prompt.
003
Power-B, Lost
Verify that the fuse for Power B is properly installed and not
OPEN.
Verify that Power Bus B is providing –48 VDC to the unit. If no
power is connected to the Power B input and there is no plan to
connect power, enter the command
AL 10-1 IG
at the prompt.
004
SPI Watchdog, Timeout
Unable to communicate with other modules. Re-seat module.
005
Shelf #2 Comm, Lost
Unable to communicate with Expansion Shelf 2. Check cables.
006
Shelf #3 Comm, Lost
Unable to communicate with Expansion Shelf 3. Check cables.
007
Shelf #4 Comm, Lost
Unable to communicate with Expansion Shelf 4. Check cables.
008
Shelf #5 Comm, Lost
Unable to communicate with Expansion Shelf 5. Check cables.
009
Detect Mdl Removed, Fault
A module has been removed from the system or is not responding
to Comms module queries. Replace the removed module with the
same type, or issue the command
CONFIG xAy REMOVE
to
remove the module information from the system database.
105
KeepAlive, SSU2000
The Keep Alive function has been enabled/ disabled.
129
Install, Comm Module
The Comms module has been installed.
130
Remove, Comm Module
The Comms module has been removed.
131
Enable, Comm Module,
COML
The Comms module has been enabled.
132
Disable, Comm Module,
COML
The Comms module has been disabled.
133
Restart, in 5 seconds,
COML
The Comms module has been rebooted (Warm boot).
144
Log In, JAY, COML, level: 2
User at indicated level has logged in.
145
Log Out, TIM, COML, level: 2
User at indicated level has logged out.
146
Auto Out, TIM, COML, level: 3
System automatically logging out a user.
147
Msg, <HELLO BILL>, COML
Message sent from a user.
148
Not Acknowledged, 1A01
Module configuration could not be obtained.
150
Module Status, Fault, 1A04
Module did not boot properly.