SymCom Motor Saver 460-SP Installation Instructions Manual Download Page 1

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!

FOLLOW NATIONAL, STATE, AND LOCAL CODES!

READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

INSTALLATION INSTRUCTIONS

FOR SYMCOM’S MOTORSAVER

MODEL 460-SP

The Model 460-SP MotorSaver

 

is a voltage monitor designed to protect 

single-phase motors regardless of size.  The MotorSaver

 is used on 190-

240 (95-120) VAC, 50 to 60 Hz motors to protect from damage caused by low 
voltage and high voltage.

CONNECTIONS

1. Mount the MotorSaver

 in a convenient location in or near the motor

control panel.  If the location is wet or dusty, the MotorSaver

 should

be mounted in a NEMA 4 or 12 enclosure.  The MotorSaver

 

 can be

mounted to a back panel using two #6 or #8 x 5/8 screws or can be
snapped onto a DIN rail.

2. Connect L1 and L2 on the MotorSaver’s terminal strip to the LINE SIDE

of the motor starter (See Figure 1).

3. Connect the output relay to the circuitry to be controlled.  For motor control,

connect the normally open contact in series with the magnetic coil of the
motor starter (See Figure 1).  For alarm operation, connect the
normally closed contact in series with the control circuit (See Figure 2).

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for Motor Saver 460-SP

Page 1: ...or near the motor control panel If the location is wet or dusty the MotorSaver should be mounted in a NEMA 4 or 12 enclosure The MotorSaver can be mounted to a back panel using two 6 or 8 x 5 8 screw...

Page 2: ...L VOLTAGE 24 240 VAC 460 SP FIGURE 1 CONTROL WIRING DIAGRAM LIGHT 3 Phase Voltage CONTROL VOLTAGE 24 240 VAC 460 SP FIGURE 2 ALARM WIRING DIAGRAM Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com...

Page 3: ...torSaver closing its output contacts For compressor applications the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the compressor For other applic...

Page 4: ...e RESTART delay After the RESTART delay the MotorSaver will energize its output contacts and the green RUN light will illuminate If the contacts do not energize and the RUN light does not illuminate s...

Page 5: ...voltage is 7 above or below the nominal voltage as selected by the LINE VOLTAGE ADJUST the MotorSaver is functioning properly If the voltage is within 7 of the selected line voltage call SymCom at 1 8...

Page 6: ...480 VA 240 VAC General Purpose 10 A 240 VAC Power Consumption 6 Watts maximum Weight 14 oz Enclosure Polycarbonate Terminal Torque 6 Inch Pounds Wire AWG 12 20 AWG Safety Marks UL UL508 File E68520 CE...

Page 7: ...tions please refer to the SymCom Terms and Conditions of Sale document DIMENSIONS Surge IEC IEC 1000 4 5 Level 3 4kv line to line Level 4 4kv line to ground ANSI IEEE C62 41 Surge and Ring Wave Compli...