 Installation and starting instructions 

SYCLOPE COOLTouch

®

 Controller for Cooling tower managements (Part 1) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation and starting instructions 

 
 
 

 
 

 
 
 

 
 

 
 
 

 
 

 
Reference: DOC0484    

 

 

 

 

 

 

 

Rev: 1

Summary of Contents for COOLTouch

Page 1: ...Installation and starting instructions SYCLOPE COOLTouch Controller for Cooling tower managements Part 1 Installation and starting instructions Reference DOC0484 Rev 1...

Page 2: ...information SYCLOPE Electronique 2021 Manual of 25 08 2021 Rev 1 Professional controller for cooling towers Product line COOLTOUCH Part 1 Installation and starting instructions Ref DOC0484 Editor SYC...

Page 3: ...n Close transparent door 17 4 Open Close the terminal cover 17 5 Tightening torque 18 a Cable gland 18 b Terminal blocks 18 6 Electrical connections 18 7 Changing the internal fuse of PO1 output 19 8...

Page 4: ...2 Numerical value entry screen 43 3 Alphanumeric keyboard 44 a Shift key 44 b Caps lock key 44 c Keyboard type key 44 d Other characters key 45 e Back key 45 f Enter key 45 g Close key 45 h Special ca...

Page 5: ...for chemical treatments The simplicity of the COOLTouch controller operations the user friendliness and the remarkable technical aspects of these controllers will ensure you benefits from their many o...

Page 6: ...uit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Changes and modifications not expressly approved by the manufacturer could...

Page 7: ...ion Action to do Element of a list or enumeration 4 Symbols and signs Identification of a continuous volage or current Identification of an alternative voltage or current Protective ground Functional...

Page 8: ...the maintenance of IP65 protection Cables used must be adapted to them in order to respect the portion index Shielded cables for connecting pH and ORP electrodes are not supplied The controller is de...

Page 9: ...the following range 100 208V Do not use the device for measurements on the network directly but only on the secondary circuit under very low safety voltage 2 User obligations The user undertakes not t...

Page 10: ...using consumable parts They must be supervised maintained and calibrated regularly using specific calibrator systems not provided with this equipment In the event of defect a surplus possible hazard o...

Page 11: ...ective 2011 65 EC this symbol means that the SYCLOPE COOLTouch controller is designed in compliance with the restrictions on hazardous substances According to low voltage directive 2014 35 UE and the...

Page 12: ...EN61326 1 Class B disruption tests comply with EN61326 2 6 Class B disruption tests comply with EN55011 Harmonics tests comply with EN61000 3 2 Harmonics tests comply with EN61000 3 3 Immunity tests c...

Page 13: ...ys PWM or On Off functions Analogical outputs 2 0 4 20mA programmable outputs Copy or control functions Purge Bleed off function By setting conductivity or volumetric setpoints 3 Radio technologies in...

Page 14: ...0 02 to 2 mg l 0 5 0 2 to 10 mg l 0 5 0 4 to 15 mg l 0 5 0 to 2000 mg l 0 5 DBDMH 0 1 to 1 mg l 0 5 0 1 to 5 mg l 0 5 0 1 to 10 mg l 0 5 0 to 2000 mg l 0 5 Free bromine 0 1 to 1 mg l 0 5 0 1 to 5 mg l...

Page 15: ...Technical characteristics and functions Page 15 57 Installation and starting instructions...

Page 16: ...s not make it difficult to operate the disconnecting circuit fuse or circuit breaker If these instructions are not observed The controller risks to be damaged The measurements can be disrupted The war...

Page 17: ...ansparent door Door locked Lift the lock and pull towards the front of the device Door opened To close and lock the transparent door Put your fingers behind the lock and bring the door with your thumb...

Page 18: ...device Before making the connections cut off the power supplies Preferably use single strand cables Otherwise it is essential to use a crimped cable ends to ensure that no strand can come into contac...

Page 19: ...you are led to using it don t forget to replace it Cut off the power supply before changing the fuse Always use a fuse identical to the original one Don t replace with a higher intensity Cut off the p...

Page 20: ...40V 50 60Hz Use a 3 point 1 5 mm2 to wire the power supply Strip the 3 wires on 7mm Pass the 3 point cable through a cable gland Connect the phase on L1 and the neutral on the N of the main terminal b...

Page 21: ...o DI5 digital for sensor 1 Input SI1 serial for UART 5V TTL a PT100 Pt1000 input RI1 Connection of the sensor on RI1 Preferably use a shielded coaxial cable Connect the sensor strand to the RI1 1 conn...

Page 22: ...Client Free chlorine Active chlorine Total chlorine Chlorite Chlorine dioxide Peroxide Bromine BCDMH Bromine DBDMH Free bromine Peracetic acid Ozone Dissolved oxygen PHMB The scale of customer can be...

Page 23: ...L min L H or m3 H in 4 20mA or impulse input Connection of a R I C Remote Input Control tank bottom or another sensor on DI1 Preferably use a two strand cable Connect one sensor strand to the DI1 sw 1...

Page 24: ...and to the DI3 21 connection Tighten the cable gland to seal e Serial input SI1 Controller has 1 serial input on which a CTFS sensor can be connected Connection of a CTFS sensor on SI1 Remove the prot...

Page 25: ...Connect the earth on PE 52 of the PO1 mains terminal block Tighten the cable gland to seal 11 Potential free relay connections FO1 to FO4 The potential free relay outputs can be used as alarm relays...

Page 26: ...oltage and current Remove the protective sheath Strip wires on 7mm Pass the cable through a cable gland Connect a cable on the midpoint COMMUN 42 of the terminal block Connect the second cable on the...

Page 27: ...contact it is used to drive pumps by their impulse input or to control an external power relay This relay can switch a maximum voltage of 48 VAC and a current of 50mA Use a 2 wire cable with a sectio...

Page 28: ...aximum load is 500 4 20mA outputs are fully configurable You can assign any parameter measured or calculated in regulation or data transfer mode Use a 2 wire cable Remove the protective sheath Strip w...

Page 29: ...t connection PWR If necessary chlorine or bromine sensors may be used that require external power Use a 2 wire cable Pass the cable through a cable gland Connect the strand of the alimentation on 24V...

Page 30: ...Wire AA n 3 of USB 485 converter to RS485 A 27 Wire BB n 4 of USB 485 converter to RS485 B 28 Wire C n 5 of USB 485 converter to PWR C 15 Tighten the cable gland to seal Blue Terminal n 3 AA RS485 Whi...

Page 31: ...S B of the electronic card in ON position If your device is the last on the line on the RS485 bus you can switch the Term RS switch on ON to activate line termination For security reasons it s imperat...

Page 32: ...he deconcentration valve must be opened at defined intervals This loss is compensated by the supply of new water To prevent corrosion and tartar formation in the cooling tower an inhibitor and or disp...

Page 33: ...n disturbed SYCLOPE COOLTouch regulator doesn t automatically start the treatment and dosing of chemical product when you switch ON Only the user can initiate the treatment after ensuring that the con...

Page 34: ...on human health and the environment 1 Main screen display a The upper banner Menu button programming Press to open the menu For more information about this part see DOC0485 General programming instruc...

Page 35: ...unication Info Press it to display communication information For more information about this part see DOC0485 General programming instructions COOLTOUCH ENG Rev1 Communication Info SSID SYCLOPE Etage...

Page 36: ...onnections to WIFI impossible See DOC0461 Communication programming instructions COOLTOUCH for more information Bleed indicator Flow switch indicator Flow switch is ON Flow switch is OFF Biocide inhib...

Page 37: ...vity channel Conductivity 1111 S cm Volume Type of measurement Measured value Unit Type of measurement Measured value Unit Value higher the scale Value lower the scale Value not displayable Value unme...

Page 38: ...ure 39 0 C Type of measurement Measured value Unit Value higher the scale Value lower the scale Value not displayable Value unmeasurable Technical alarm Servitude notifications area Polarization in pr...

Page 39: ...press on of the main screen c Biocide Example with Biocide A To open the detailed display screen press on of the main screen FO1 Biocide A INACTIVE Start biocide cycle Clear Fill Total injection time...

Page 40: ...splay screen press on of the main screen e Dosing mode To open the detailed display screen press on of the main screen FO3 Inhibitor INACTIVE Start biocide cycle Clear Fill Total injection time Tank l...

Page 41: ...ge 41 57 Installation and starting instructions f Tower management To open the detailed display screen press on of the main screen RO1 Operating INACTIVE Manuel start tower Stop Tower state unknown Ne...

Page 42: ...mation Mesure information 27 08 2021 15 02 27 08 2021 15 02 Controller state Enable Halt Circulation Bleed state Free Biocide A state Free Biocide B state Free Inhibitor state Free Dispersant state Ta...

Page 43: ...n entering a numeric value Depending on the values to be entered some keys may be greyed out because they are not used for the expected value The decimal symbol changes automatically according to the...

Page 44: ...ps lock key This key switch the keyboard from lowercase to uppercase and keep it in uppercase In this position the Shift kay allows a temporary toggle from capital to small Key released and inactive p...

Page 45: ...closes the keyboard while saving the changes Tap to close and save g Close key This key closes the keyboard without saving the changes Press to close without saving h Special case of access to accente...

Page 46: ...nge the direction c Unique selection button Press to active state select d Input button Press to open numerical keyboard e Action button Save a configuration Delete a configuration Back button back to...

Page 47: ...the event that the list is longer navigation buttons will appear to move through the list Simple list List with navigation buttons Close the list without selection Move the list down Move the list up...

Page 48: ...levels in the programming by clicking on one of the menu buttons Example Icons in the navigation bar correspond to the identification icons in the top left of each screen h Lock symbol Padlock symbol...

Page 49: ...n 3 CTFS conductivity Volume Bio A Inhibitor Chlorine o Configuration 4 Volumetric mode Volume Bio A Inhibitor o Configuration 5 Resistive conductivity Volume Bio A Inhibitor Sensors list Select desir...

Page 50: ...nt to clear the current configuration You may or may not reset the User or Communication configurations in addition to the Setup and Configuration section It s also possible if technical support is ne...

Page 51: ...Annexes Page 51 57 Installation and starting instructions...

Page 52: ...s box DATE TIME Menu User Date and time parameters change Automatic daily saving time UTC 1 00 Brussels Copenhagen Madrid Paris June 2019 Friday 19 10 15 50 12H 24H mm dd yy dd mm yy DST UTC 2 00 19 0...

Page 53: ...zone is on the centre part of the selection Wait for automatically shutdown to account for new time zone UTC 1 00 Central Africa West UTC 1 00 Amsterdam Berlin Bern Rome Stockholm Vienna UTC 1 00 Bel...

Page 54: ...off the power supply Always use the same battery as the original Open the transparent door and unscrew the 4 front screws using an appropriate screwdriver Carefully disconnect the connection flat cabl...

Page 55: ...e between the cards and reassemble the front panel using the 4 fixing screws Don t overtighten because the screws are fixed in the plastic case Reconnect the flat cable and replace the front panel bef...

Page 56: ......

Page 57: ...CLOPE Electronique S A S Z I A ropole Pyr n es 64 230 SAUVAGNON Tel 33 05 59 33 70 36 Fax 33 05 59 33 70 37 Email service technique syclope fr 2020 by SYCLOPE Electronique S A S Subject to modificatio...