background image

 

CB1 TAC3 CA - ALARMS

                                                       

                                        Technical documentation

                                               

(v.10/2007) 

 
 

The control box CB1 TAC3 CA features 4 alarms:  
 
- an alarm on pressure rise. 
- an alarm on fan failure. 
- initialisation alarms. 
- alarm of non respect of the assignment. 

 
Wiring diagram: 

see appendix

 

1. overpressure alarm. 

 

This  alarm  indicates  a  variation  of  calculated  pressure  on  the  fan  with  regard  to  the  value  of  the  initialized  pressure  of 
reference. The alarm levels are calculated using the system curve principle. 
When this alarm is activated: : 

LED 

Alarm

 on CB is on. 

PRESSURE ALARM

 appears on the screen. 

Relay 

R2

 of the optional SAT3 is closed. 

LED above realy 

R2

 of option SAT3 is on. 

 

Example of Initialisation of pressure alarm 

 
It is very important to install the fan properly in the real working conditions. 
The setup is done accordingly to the configuration sequences of the control circuit: 
 
1) Setting of the 

∆Pa increment; suppose ∆Pa=80Pa (for instance maximum filter pressure)  

 

Entrer this value during the initialisation procedure. This value will be added to the reference pressure resulting from the 
reference airflow chosen hereunder. 
 
2) Initialisation of the reference pressure: 

 

During initialization sequence select  NEW Pa REF ? YES then press ENTER. 
Suppose (m³h INIT)= 1250 m³/h, enter this value then press ENTER.  
The fan will start running and reach this value, whatever the status of K1/K2/K3 is. 
While reaching the reference working point the display shows the following instant values: 
Pa REF INIT  
xxxx m³h and xxxx Pa.  
and LED Alarm is blinking. 
 
When  reference  airflow  (1250  m³/h)  is  reached,  the  actual  pressure  (for  example  122  Pa)  is  memorized  and  the  alarm 
reference point becomes 1250 m³/h  - (122+80)Pa. The fan starts to run as programmed. 
 
4 types of  problems could occur while doing this: 

 

Text displayed  

Description 

FAN ALARM 

CHECK POWER 
SUPPLY AND  
CABLES CONNECT. 
THEN PRESS 
ON RESET.  
IF NOT SOLVED 
REPLACE CABLE  
OU CB OU MOTOR 

Describes a fan function default. Check wiring, connections and 230V supply.   
Otherwise the problem can be caused by defective wire, control circuit or motor. 
(text is displayed on several successive screens). 
 
Alarm LED is lit, relay R1 is closed and relay LED is also lit. 
 
 

Pa INIT ALARM 

AIRFLOW TOO LOW  
DUE TO TOO HIGH 
PRESSURE  
REDUCE PRESSURE  
OR FLOW 

Actual airflow < requested airflow: the requested airflow is located at a pressure 
level the fan cannot reach. Change the air system, or the airflow requested, or a 
use bigger fan. (1) 
Text is displayed on several successive screens 
 

Reviews: