AMI Codes-II CC
Program List and Explanations
A-96.250.581 / 220616
87
5 Installation
5.1 Sensors
5.1.1
Dimension
: The measuring value can be displayed as ppm or mg/l
5.1.2
Interpolation:
Yes
: Calculates the average of the 2 last measuring values of free
chlorine measurement. Use this mode to avoid high spikes in the
control loop.
No
: The true measuring value is displayed and available at the
outputs.
5.1.3
Ref. Verification:
Set absorbance value of verification kit according
to label.
Range: 0.200–0.600
5.1.40
Standards:
Program the two standard solutions for the calibration
of the pH electrode. If pH electrode is not connected the pro-
grammed standards are not active.
Range: 1.00 pH - 13.00 pH
5.1.5
Cleaning:
Program if one or two solutions are used on Cleaning
module. See
Range: 1 Solution, 2 Solutions
5.2 Signal Outputs
5.2.1&5.2.2
Signal Output 1 and 2:
Assign process value, the current loop
range and a function to each signal output.
NOTICE:
The navigation in the menu <Signal Output 1> and
<Signal Output 2> is equal. For reason of simplicity only the
menu numbers of Signal Output 1 are used in the following.
5.2.1.1
Parameter:
Assign one of the process values to the signal output.
Available values:
Free av. chlorine (
Free available chlorine
)
Total chlorine 1
Total chlorine 2
Calc. monochl. (
Calculated monochloramine
)
Calc. comb. cl. (
Calculated combined chlorine
)
Calc. dichloramine (
Calculated dichloramine
)
Temperature
Sample flow
pH