4-5
Interfaces of the Device
4.1.2.2
Termination
For point-to-point connections, always activate the termination. For multipoint con-
nections, only activate the termination at the cable end.
Figure 4-4
Block diagram termination RS422 / RS485
Legend for table:
I = Switch ON
- = Switch OFF
Table 4-5
Resistor values - termination RS422 / RS485
Designation
Value
R1, R3
510 Ohm
R2
150 Ohm
R4
120 Ohm
The switch positions for ON or OFF are printed onto the termination switch. Only the
specified switch positions are allowed.
Table 4-6
Termination switch
S1
S2
S3
S4
Function
Transmit-
ter
Receiver
I
I
I
I
Termination is ON
–
–
–
–
Termination is OFF