10
Command
value
Response
Description
AT
--
OK
Test RS232
communication with
module
Node Address =
<value>
<value> =
0 : automatic
node address
<
value
> 1 thru 247 :
Static address range
>Node Addr =
value
Where value = new address assigned to
the Node
Set the node address to
either automatic or
static address
NwId=<
value
>
<value> =
1 through 15
>NwID = <
value
>
value = new value for Network ID
Set the network ID.
Must have the same
value for all modules
in the same network
Nw Scan
--
>
Node Address=
addr
, Hops=
hops
returns the address and hop count for
each node
Performs a live Scan
and report the address
and hop count for all
nodes in the current
network
ver
--
>NW Stack Ver=x.xx
>Modbus Stack Ver=x.xx
Returns the version
number of the modbus
stack and network
stack
Blink Led =
<
addr
>,<
time
>
<
value
> = remote node
address
<
time
> = duration in
seconds to keep blinking
the LED on remote node.
If time = 0 , the Led will
blink forever
>OK :
Node blink command sent successfully
>ERROR : Destination not found
Unable to locate remote node
Blink the Red LED on
remote node for a
predetermined amount
of time
Factory Defaults =!Sutron!
--
OK
Restores all settings to
factory defaults